SELECTING THE LOCATION FOR THE INDOOR UNIT
Required Minimum Space for Installation and Service.
Provide a check port on the piping side ceiling for repair and maintenance.
Install the indoor unit once the follo
wing conditions are satisfi
ed and after receiving the customer approval.
1. The indoor unit must be within a maintenance space.
2. The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading of air
throughout the room.
Top view
(Unit:mm)
Inspection hole
Control box
(600 x 600)
600
<Front>
1000
600
Front view
Ha
Above 250cm
(Recommended)
TYPE Ha
S-60PE1R5B
290
S-71PE1R5B
360
S-100PE1R5B
360
S-125PE1R5B
430
S-145PE1R5B
430
* The Ha is necessary for the access to the
top of the unit for repair.
* If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is
decreased.
INSTALLATION OF INDOOR UNIT
Fig. 1-11-19
POSITION OF SUSPENSION BOLT
540
700
1160
1100
1~3mm
Drainage hole
Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
Install the unit leaning to a drainage hole side as a
fi
gure for easy water drainage.
Fig. 1-11-20
H
F
E
E
F
F
F
G
79
81
TYPE E F G H
S-60PE1R5B
130
33.1
290
118
S-71PE1R5B
S-100PE1R5B
195
35.7
360
50
S-125PE1R5B
S-140PE1R5B
260
38.2
430
121.5
Fig. 1-11-21
(unit: mm)
SM830266-00_大洋州向けR32シングルTD&SM.indb 72
18/03/29 10:20:58
Summary of Contents for Inverter R32 Series
Page 93: ...1 10 10 1 SM830266 00_ R32 TD SM indb 10 18 03 29 10 19 58...
Page 94: ...1 10 11 1 SM830266 00_ R32 TD SM indb 11 18 03 29 10 19 58...
Page 95: ...1 10 12 1 SM830266 00_ R32 TD SM indb 12 18 03 29 10 19 59...
Page 96: ...1 10 13 1 SM830266 00_ R32 TD SM indb 13 18 03 29 10 20 00...
Page 241: ...MEMO 1 13 11 SM830266 00_ R32 TD SM indb 11 18 03 29 10 21 37...