If you wish to change the selected indoor unit, follow the
step (2).
<Procedure of CZ-RTC4>
Stop the system before performing these steps.
(1) Press and hold the
,
and
buttons
simultaneously for 4 seconds or longer.
(2) If group control is in effect, press the
button to set.
At this time, the fan at the indoor unit begins and select
the address (unit No.) of the indoor unit operating.
(3) Designate the item code “
” by adjusting the
Temperature Setting
/
buttons.
=91
=90
=92
=93
Electrical component box
(4) Press the timer time
/
buttons to select the
desired setting data.
Flap position
1
2
3
4
5
* Setting data “
”
Setting data
Flap position during operation
Without separate setting
Swing
Move to position
1
and stay
Move to position
2
and stay
Move to position
3
and stay
Move to position
4
and stay
Move to position
5
and stay
N OT E
The flap swings during the operation under “Setting
the Flap Separately”.
At this time, the unselected flaps are moved to the
position
1
.
A
°
°
(1)
(5)
(6)
(2)
(2)
(4)
(3)
(4)
YYYY
XX
(5) Press the
button.
(The display stops blinking and remains lit, and setting is
completed.)
If you wish to change the selected indoor unit, follow the
step (2).
(6) Press the
button to return to normal remote
controller display.
N OT E
See “Section 8. HOW TO INSTALL THE WIRELESS
REMOTE CONTROLLER RECEIVER”.
HOW TO INSTALL WIRELESS REMOTE
CONTROLLER
CAUTION ON INSTALLATION
Criteria for Human Detection Area
A place where the blind angle of the Human Detection Sensor cannot detect human.
Install the panel for cassette (ECONAVI type) so that human motion can be detected.
If there is a heat source or cooling unit in the detection area, the sensor cannot occasionally detect properly.
The Floor Temperature Sensor detects within the sensor area of Human Detection Sensor.
Human Detection Sensor
Floor Temperature Sensor
Detection area of Human Detection Sensor
1 m above floor visual range
Installation
height:
2.7 - 5 m
Detection area of Floor Temperature Sensor
Approx. ø7 - 9 m
Criteria of human detection sensor area
Installation height of indoor unit 2.7 m : Approx. ø7 m
Installation height of indoor unit 4 m : Approx. ø8 m
Installation height of indoor unit 5 m : Approx. ø9 m
Do not install at the following locations. (Cause of trouble and malfunction)
• Humid, oily, frequent vibration
• Direct sunlight and near by heat source
• Frost
SM830266-00_大洋州向けR32シングルTD&SM.indb 44
18/03/29 10:20:35
Summary of Contents for Inverter R32 Series
Page 93: ...1 10 10 1 SM830266 00_ R32 TD SM indb 10 18 03 29 10 19 58...
Page 94: ...1 10 11 1 SM830266 00_ R32 TD SM indb 11 18 03 29 10 19 58...
Page 95: ...1 10 12 1 SM830266 00_ R32 TD SM indb 12 18 03 29 10 19 59...
Page 96: ...1 10 13 1 SM830266 00_ R32 TD SM indb 13 18 03 29 10 20 00...
Page 241: ...MEMO 1 13 11 SM830266 00_ R32 TD SM indb 11 18 03 29 10 21 37...