ECONAVI TEST OPERATION
Preparation: Refer to the manuals of the indoor unit and turn
on the main power switch in advance.
Human detection cannot be made for approx.
90 seconds when switched on the power
because the human detection sensor is set in
initial setup.
1. Press three buttons.
Keep pressing the
,
and
buttons
simultaneously for more than 4 seconds.
The “Maintenance func” menu appears on the screen.
2.
Select “0. ECONAVI info.” from the menu command.
By pressing the
/
buttons, select
“0. ECONAVI info.” and press the
button.
3.
Select “Error found” from the menu command.
By pressing the
/
buttons, select “Error
found” and press the
button.
4.
Check the sensor status shows “Normal”.
(By pressing the
/
buttons, the status of
each indoor unit can be scrolled on the screen.)
The sensor status of all indoor units are displayed.
•
“Normal”: The sensor on the panel for cassette
(ECONAVI type) works normally.
•
“Preparing”: The sensor on the panel for cassette
(ECONAVI type) is set in initial setup.
Confirm that “Normal” appears within 90 seconds.
•
“Unsupported”: Indoor units not available for ECONAVI
function.
The test run procedure described above is over. If any
display appears other than “Normal” or “Preparing” even
though the ECONAVI panel is connected, follow the Step 5
below.
* “1-1”, “1-2” mean indoor unit No. If the indoor unit is without
ECONAVI panel, “Not connected” appears.
* “Sensor 1” means optional ECONAVI sensor
(CZ-CENSC1). If not connected, “Not connected” appears
besides “Sensor 1” on the screen.
5.
If the sensor status shows other than “Normal”,
“Preparing”,
If the sensor status shows “Error” or “Not connected”
although the panel for cassette (ECONAVI type) is
connected, the following symptom may have occurred.
Specify the applicable indoor unit and check the sensor.
“Error”: The sensor may possibly be damaged.
”Not connected”: The wiring between the indoor unit and
sensor may possibly be disconnected.
* The specified indoor unit can be confirmed by the flap
operation.
Confirmation method:
1
Finish the maintenance function.
Press the
button to show the maintenance
function display and then press the
button.
2
Operate the flap.
By pressing the
button, select the applicable
“Indoor Unit No.” in the list of “2. FLAP” and then
make flap setting. The indoor unit which responds to
the flap setting becomes available.
When the indoor unit is specified, turn off the main
power switch and disconnect the connector of sensor
wiring from the PCB. Then reconnect it. Turn on the
main power switch and repeat the Steps 1 to 4 described
above. Confirm the display shows “Error found”. If the
display shows “Error” or “Not connected” on the screen
again, it is necessary to replace the panel for cassette
(ECONAVI type) with a new one.
EXTERNAL DEVICE INTERLOCK
Example of wiring:
This is an example of the combination systems which extract optional output signal by the service wire and relay (field supply).
When actuating the external device interlock, use the thermostat signal.
OPTION Connector (CN060) Output external signals
PAW-OCT: Panasonic has developed an optional accessory (consisting of plug + wires) called
PAW-OCT to enable an easy connection to this OPTION Connector (CN060).
With the combination of the T10 and the OPTION Connector (CN060) an external control of the I_U is possible!
6P (WHITE): OUTPUTS EXTERNAL SIGNALS AS SHOWN IN THE FIGURE BELOW.
1
2
3
4
5
6
1
2
3
4
5
6
OPTION
(white)
Relay (DC 12V, field supply) (Note)
Indoor unit control
PCB (CR1)
Note: The relay must be installed at a
distance of 2 m or less from the PCB.
Fan signal
DC 12V
Heat start
signal
Cool start
signal
Thermostat
signal
Defrost signal
NOTE
The external output signal from the air conditioner is supplied for the purpose of controlling the external devices. If the air
conditioner does not operate, take measures that the movement of external connecting devices can transfer to the safety
zone in advance.
The external output signal from the air conditioner is turned off when the blackout occurs. If any special considerations are
needed in case of blackout, provide an external circuit.
Use the thermostat signal.
SM830266-00_大洋州向けR32シングルTD&SM.indb 54
18/03/29 10:20:40
Summary of Contents for Inverter R32 Series
Page 93: ...1 10 10 1 SM830266 00_ R32 TD SM indb 10 18 03 29 10 19 58...
Page 94: ...1 10 11 1 SM830266 00_ R32 TD SM indb 11 18 03 29 10 19 58...
Page 95: ...1 10 12 1 SM830266 00_ R32 TD SM indb 12 18 03 29 10 19 59...
Page 96: ...1 10 13 1 SM830266 00_ R32 TD SM indb 13 18 03 29 10 20 00...
Page 241: ...MEMO 1 13 11 SM830266 00_ R32 TD SM indb 11 18 03 29 10 21 37...