1
1-11-37
Finishing the Installation
After finishing insulating and taping over the tubing, use sealing
putty to seal off the hole in the wall to prevent rain and draft
from entering.
Apply putty here
Tubing
HOW TO INSTALL THE TIMER REMOTE
CONTROLLER OR HIGH-SPEC WIRED
REMOTE CONTROLLER (OPTIONAL PART)
N OT E
See “Section 2. TEST RUN”.
Accessories Supplied with Unit
(4-Way Cassette)
Part Name
Figure
Q’ty
Remarks
Full-scale
installation
diagram
1
Printed on
container box
Washer
8
For suspension
bolts
Screw
4
For full-scale
installation diagram
Insulating tape
2
For gas and liquid
tube flare nuts
Flare insulator
1
For liquid tube
Flare insulator
1
For gas tube
Drain hose
1
Hose band
1
For securing drain
hose
Part Name
Figure
Q’ty
Remarks
Packing
1
Drain insulator
1
Clamper
4
For electrical wiring
Operating
Instructions
1
Installation
Instructions
1
Use M10 for suspension bolts.
Field supply for suspension bolts and nuts.
Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local
source, you will need:
1.
Deoxidized annealed copper tube for refrigerant tubing.
2.
Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness of the
insulation should be not less than 8 mm.
3.
Use insulated copper wire for field wiring. Wire size varies
with the total length of wiring. See the section
“1-10. E
lectrical Wiring
” for details.
CAUTION
Check local electrical codes and regulations before
obtaining wire. Also, check any specified instructions or
limitations.
Additional Materials Required for Installation
1.
Refrigeration (armored) tape
2.
Insulated staples or clamps for connecting wire (See your
local codes.)
3.
Putty
4.
Refrigeration tubing lubricant
5.
Clamps or saddles to secure refrigerant tubing
6.
Scale for weighing
SM830266-00_大洋州向けR32シングルTD&SM.indb 37
18/03/29 10:20:21
Summary of Contents for Inverter R32 Series
Page 93: ...1 10 10 1 SM830266 00_ R32 TD SM indb 10 18 03 29 10 19 58...
Page 94: ...1 10 11 1 SM830266 00_ R32 TD SM indb 11 18 03 29 10 19 58...
Page 95: ...1 10 12 1 SM830266 00_ R32 TD SM indb 12 18 03 29 10 19 59...
Page 96: ...1 10 13 1 SM830266 00_ R32 TD SM indb 13 18 03 29 10 20 00...
Page 241: ...MEMO 1 13 11 SM830266 00_ R32 TD SM indb 11 18 03 29 10 21 37...