17
ENGLISH
r
Signal inputs
Optional Thermostat
L N =AC230V, Heat, Cool=Thermostat heat, Cool
terminal
SG signal
Dry contact Vcc-Bit1, Vcc-Bit2 open/short
(System setup necessary)
Switching SW (Please connect to the 2 contacts
controller)
Heat/Cool SW
Dry contact Open=Heat, Short=Cool (System
setup necessary)
External comp.SW
Dry contact Open=Comp.ON, Short=Comp.OFF
(System setup necessary)
Demand signal
DC 0~10V (System setup necessary)
Please connect to the DC 0~10V controller.
Outputs
Mixing valve
AC230V N=Neutral Open, Close=mixture direction
Operating time: 30s~120s
Pool pump
AC230V
Solar pump
AC230V
Zone pump
AC230V
Thermistor inputs
Zone room
sensor
PAW-A2W-TSRT
Buffer tank
sensor
PAW-A2W-TSBU
Pool water
sensor
PAW-A2W-TSHC
Zone water
sensor
PAW-A2W-TSHC
Solar sensor
PAW-A2W-TSSO
Recommended External Device Specifi cation
•
This section explains about the external devices (optional)
recommended by Panasonic. Please always ensure to use the
correct external device during system installation.
•
For optional sensor.
1. Buffer tank sensor: PAW-A2W-TSBU
Use for measurement of the buffer tank temperature.
Insert the sensor into the sensor pocket and paste it on the
buffer tank surface.
40
black
brown
blue
Dimensions (mm)
Ø6
2. Zone water sensor: PAW-A2W- TSHC
Use to detect the water temperature of the control zone.
Mount it on the water piping by using the stainless steel metal
strap and contact paste (both are included).
93
70
35
Dimensions (mm)
3. Outdoor sensor: PAW-A2W-TSOD
If the installation location of the outdoor unit is exposed to direct
sunlight, the outdoor air temperature sensor will be unable to
measure the actual outdoor ambient temperature correctly.
In this case, optional outdoor temperature sensor can be fi xed
at a suitable location to more accurately measure ambient
temperature.
70
93
46
Dimensions (mm)
4. Room sensor: PAW-A2W- TSRT
Install the room temperature sensor to the room which requires
room temperature control.
Dimensions (mm)
86
86
60
30
5. Solar sensor: PAW-A2W-TSSO
Use for measurement of the solar panel temperature.
Insert the sensor into the sensor pocket and paste it on the solar
panel surface.
40
black
brown
blue
Dimensions (mm)
Ø6
6. Please refer to the table below for sensor characteristic of the
sensors mentioned above.
Temperature
(°C)
Resistance
(k
Ω
)
Temperature
(°C)
Resistance
(k
Ω
)
30
5.326
150
0.147
25
6.523
140
0.186
20
8.044
130
0.236
15
9.980
120
0.302
10
12.443
110
0.390
5
15.604
100
0.511
0
19.70
90
0.686
-5
25.05
80
0.932
-10
32.10
70
1.279
-15
41.45
65
1.504
-20
53.92
60
1.777
-25
70.53
55
2.106
-30
93.05
50
2.508
-35
124.24
45
3.003
-40
167.82
40
3.615
35
4.375
•
For optional pump.
Power supply: AC230V/50Hz, <500W
Recommended part: Yonos 25/6: made by Wilo
•
For optional mixing valve.
Power supply: AC230V/50Hz (input open/output close)
Operating time: 30s~120s