13. SG ready
Initial setting: No
System setup
17:26, Wed
Solar connection
External error signal
Demand control
SG ready
Select
Confi rm
Switch operation of heat pump by open-short of 2 terminals.
Setting belows are possible
SG signal
Working pattern
Vcc-bit1
Vcc-bit2
Open
Open
Normal
Short
Open
Heat pump and Heater OFF
Open
Short
Capacity 1
Short
Short
Capacity 2
Capacity setting 1
- Heating capacity ___%
Set by SG ready setting of remote controller
- DHW capacity ___%
Capacity setting 2
- Heating capacity ___%
- DHW capacity ___%
14. External Compressor SW
Initial setting: No
System setup
17:26, Wed
External error signal
Demand control
SG ready
External compressor SW
Select
Confi rm
Set when external compressor SW is connected.
SW is connected to external devices to control power consumption, ON signal will
stop compressor’s operation. (Heating operation etc. are not cancelled).
(NOTE) Does not display if there is no Optional PCB.
If follow Swiss standard power connection, need to turn on DIP SW of main unit
PCB. ON/OFF signal used to ON/OFF tank heater (for sterilization purpose)
15. Circulation Liquid
Initial setting: Water
System setup
17:26, Wed
Demand control
SG ready
External compressor SW
Circulation liquid
Select
Confi rm
Set circulation of heating water.
There are 2 types of settings, water and anti-freeze function.
(NOTE) Please set glycol when using anti-freeze function.
It may cause error if setting is wrong.
16. Heat-Cool SW
Initial setting: Disable
System setup
17:26, Wed
SG ready
External compressor SW
Circulation liquid
Heat-Cool SW
Select
Confi rm
Able to switch (fi x) heating & cooling by external switch.
(Open) : Fix at Heating (HDHW)
(Short) : Fix at Cooling (CDHW)
(NOTE) This setting is disabled for model without Cooling.
(NOTE) Does not display if there is no Optional PCB.
Timer function cannot be used. Cannot use Auto mode.