Chapter 3. Operating Instructions
86
PanaFlow™ MV80, MV82 & MV84 User’s Manual
3.5.9
The Energy Menu for EMS Energy Meters Only
There are several possibilities regarding the measurement of water or steam energy, given the location of the meter
and the use of a second RTD.
below summarizes the possibilities:
Table 3: Configuration Options
Fluid
Meter Location
Second RTD
Measurement
Water
“Sent” Flow Line
“Return” Flow Line
Change in Energy
Water
“Return” Flow Line
“Sent” Flow Line
Change in Energy
Water
“Sent” Flow Line
None
Outgoing Energy
Steam
“Sent” Flow Line
“Return” Flow Line (condensate)
Change in Energy
Steam
“Sent” Flow Line
None
Outgoing Energy
To use the above options, you must properly configure the meter in the
Energy Menu
) by
completing these steps:
1.
Loc in Sent Flow?
Select
Yes
or
No
based on where the meter is located. Refer to
above.
2.
Heating System?
Select
Yes
for a hot water system used for heating. Select
No
for a chilled water system used for
cooling. Always select
Yes
for a steam system.
3.
% Returned.
Select a
number between 0% and 100%
. Estimate the amount of water that returns. It is usually 100%,
or can be less than 100% if historical data shows the amount of makeup water used. If a second RTD is not used,
set to 0%. When 0% is selected, the energy calculation represents the outgoing energy only (no return energy is
subtracted).
Note:
The meter ships from the factory assuming 0% return and has a 1000 ohm resistor installed in the RTD #2
wiring location. This needs to be removed if the meter is to be used in a manner other than with 0% return
and with the customer-supplied RTD in its place.