+ Pwr
– Pwr
DC Power
18 to 36 VDC @300 mA Max.
DC Common
PanaFlow™ MV80, MV82 & MV84 User’s Manual
41
Chapter 2. Installation
Figure 34: DC Power Connections
2.6.2
4-20 mA Output Connections
The standard PanaFlow meter has a single 4-20 mA loop. Two additional loops are available on the optional
communication board. The 4-20 mA loop current is controlled by the meter electronics. The electronics must be
wired in series with the sensor resistor or current meter (see
below). The current
control electronics requires 12 volts at the input terminals to operate correctly.
4-20 mA +
4-20 mA –
4-20 mA voltage = +V
mA
+V
Meter
R > 250
–
L
–V
For Hart Communications
signal loop must have a
minimum of 250 ohms load
resistance R .
L
For AC and DC
powered meters
Figure 35: Isolated 4-20 mA Output with External Power Supply
+ Pwr
– Pwr
DC Power
4-20 mA +
4-20 mA –
DC Common
only
mA Meter
For HART
communications,
the signal loop must
have a minimum of
250 ohms load
resistance.
R > 250 Ohm
L
DC powered meters
Figure 36: Non-Isolated 4-20 mA Output Using Meter Input Power Supply
+ 24 VDC
– 24 VDC
4-20 mA +
4-20 mA –
Meter Provided
mA Meter
For HART
communications,
the signal loop must
have a minimum of
250 ohms load
resistance.
R > 250 Ohm
L
AC units only.
DC Power
Figure 37: Isolated 4-20 mA Output Using Meter Provided Power Supply