PanaFlow™ MV80, MV82 & MV84 User’s Manual
23
Chapter 2. Installation
2.3.2
Installing Flow Meters with a Compression Connection (cont.)
Example:
To install a Series MV82 meter with a standard probe (S = 29.47 inches) into a 14 inch schedule 40 pipe, the following
measurements (in inches) are taken:
• F = 3 inches
• R = 5 inches
• t = 0.438 inches
Then, using the formula given in
, the insertion length for this example is 21.03 inches. Insert the
stem through the fitting until an insertion length of 21.03 inches is measured with a ruler.
Compression Nut
Stem Housing
2-inch NPT
Connection
Compression Nut
Sensor Head
Flange
Connection
Sensor Alignment
Pointer
Encloser Adapter
Stem
Stem Housing
Figure 16: Flow Meter with a Compression Type Fitting