See Roof
Pitch Table
Adjacent
Structures
or Fence
48”
(122 cm)
36”
(91.5 cm)
24”
(61 cm)
Figure 34: Roof Pitch Table
Figure 35: Wall and Roof Terminal Clearances
Vertical Roof Termination
Only the following 5 x 8" vent terminations are approved for use with this fireplace:
(Use of any other vent terminations is not allowed.)
ICC EXCELDirect®
TM – 5SVT
DuraVent DirectVent® Pro
58DVA – VCH
All other sections of pipe and elbows listed by the vent manufacturer can be used. Follow the vent pipe
manufacturers installation instructions. Use all shields, firestops and vent pipe supports as required by
the vent manufacturer.
NOTE: Mixing venting components from different manufacturers is not permitted.
NOTE: The chase must be properly sealed at the ceiling level or between floors in a multilevel
installation. Use a firestop, vent pipe shield or attic insulation shield when penetrating interior
walls, floor or ceiling.
Roof Pitch Table
(minimum)
ft.
m
Flat to 6/12
1.00
0.30
Over 6/12 to 7/12
1.25
0.38
Over 7/12 to 8/12
1.50
0.46
Over 8/12 to 9/12
2.00
0.51
Over 9/12 to 10/12
2.50
0.76
Over 10/12 to 11/12
3.25
0.99
Over 11/12 to 12/12
4.00
1.22