34
Device settings -> H2 Process settings -> Heating mode
H2 Process settings
Heating mode
Floor heating, damp rooms
Floor heating, normal
Radiator heating, normal
Radiator heating, steep curve
Constant temp. controller
Device settings> H2 Prosess settings
H2 Process settings
In use >
Heating mode
Radiator heating, normal >
Actuator selection
0-10V >
Actuator driving time
150 s >
Heating curve type
3-point heating curve >
Name of control circuit
Radiator circuit >
.Actuator selection
0-10 V
2-10V
3
Actuator driving time
75 s
min: 5 s max: 300 s
Heating curve type
3-point heating curve
5-point heating curve
Name of control circuit
Approve: Press OK a few seconds
Cancel: Press ESC a little while
R
a
d
i
a
t
o
r
c
i
r
c u
i
t
Device settings> H2 Prosess settings
H2 not in use
H2 in use
Heating mode:
Actuator selection:
Actuator driving time:
Selecting the control circuit type:
Changing the name of a control circuit:
The extension unit, supply water sensor and the second control
circuit’s actuator are optional equipment that must be obtained
seperately. Connect the H2 supply water sensor and the H2 circuit
actuator to the extension unit. Connect the extension unit to the
controller via the RJ45.2 connector.
Taking the H2 control circuit into use:
The controller automatically labels the H2 control circuit according
to the selected heating mode. Additional information about different
heating modes on p. 26.
When the H2 control circuit is taken into use,
the controller automatically reserves
regulators’s measurement channel 5 for the
H2 supply water temperature measurement.
A 24VDC-controlled actuator can be used in the
H2 control circuit. The power supply coming
from the EH-800 controller to the extension unit
is sufficient for an actuator having a maximum
of 24VDC/3W (e.g., Belimo HTC24-SR).
(connection to the extension unit’s strip con-
nectors 7 or 8). If you use a higher-powered ac-
tuator or an ac-powered actuator, the power
must be supplied by a separate transformer
and only 0 (2) …10V control is taken from the
extension unit (strip connector 9).
Here you can select whether to use a 3 point or 5 point curve.
A 3 point curve is a default and the controller prevents selection of a
wrong-shaped curve. Additional information about curves on p. 29.
See page 30.
Give the actuator a run time. The run time indicates how many se-
conds go by if the actuator drives a valve nonstop from a closed po-
sition to an open position.
Initiation of the second control circuit and relay controls on pa-
ge 32-35. These functions can be taken into use if the controller
is connected to the extension unit, OUMAN EXU-800 (optional
equipment).
L2 Menovesianturin
kytkentä
H2 Supply water
sensor (channel 5 in
regulator)
Extension unit
EXU-800
11
(UI)
H2 Process settings
In use >
Käytössä
Device settings> H2 Prosess settings
H2 actuator connection
8 (
24 VDC OUT
)
24 VDC
0 - 10 V
9 (Y)
Extension unit
EXU-800
max. 24 VDC/3W actuator
e.g. Belimo HTC24-SR