11
Basic menu: Settings
The EH-800 controller’s settings are divided into two groups; main settings and less frequent-
ly adjusted special settings which can be seen by pressing OK for a number of seconds. The-
se settings are set into the settings menu. Press OK again for a number of seconds to hide
the settings.
Changing a setting:
Turn the control knob until the setting to be changed appears against a
black background. Press OK to open a new window in which the changes are made. Press Esc
to exit..
Locking settings:
Lock the settings to prevent unauthorized persons from changing settings.
The controller will then ask for the locking code before it lets you change settings. (see p. 42).
This section illustrates main settings. Special settings are illustrated on pages 46-50.
Can be set when the heating mode is the constant temperature controller.
Basic room temperature setting for the controller set by the user. The room temperature can be
set when room temperature measurement has been taken into use. The room temperature set-
ting range can be increased or limited between 0.0...95.0 °C (see room temperature setting ran-
ge min/max, p. 47 in special maintenance settings).
Amount of temperature drop set by the user.
(factory setting; 6 °C with radiator heating, 2 °C with floor heating).
If room temperature measurement has been taken into use, the temperature drop is given di-
rectly as a room temperature drop.
A big temperature drop set by the user (factory setting; 16 °C with radiator heating, 6 °C with
floor heating). If room temperature measurement has been taken into use, the big temperatu-
re drop is given directly as a room temperature drop.
0.0...95.0°C
5.0...50.0°C
(0.0...95.0°C)
0...90°C
0...90°C
0...90.0°C
0...90°C
0...90°C
0...90.0°C
15.0°C
21.0°C
6°C
2°C
1.5°C
16°C
6°C
5.0°C
Supply water setting
Room temperature
Temperature drop
Supply water (radiator h.)
Supply water (floor h.)
Room temperature
Big temperature drop
Supply water (radiator h.)
Supply water (floor h.)
Room temperature
Setting:
Factory-
setting
Range:
Information about settings:
Basic menu -> H1 (H2) Settings
Temperature drops can be activated by the controller’s time program, home-away
function or the controller’s forced control.
> H1 Radiator heating > Settings
Room temperature
21.0 °C >
Temperature drop( room temperature )
1.5 °C >
Big temperature drop ( room temp )
5.0 °C >
Supply water min limit
12.0 °C >
Room temperature
21.0°C
min: 0.0 max: 95.0