The room temperatur alarm settings are
displayed if the room sensor is connected.
The amount of deviation between the measured supply water temperature and the controller de-
termined supply water temperature which causes an alarm when the deviation has lasted for the
time of the deviation alarm delay. To take the deviation alarm from use, set the setting outside of
the setting range. The deviation alarm is not allowed when; heating is on summer stop (see p. 12),
the controller is not on automatic or during the summer when the outdoor temperature is above
10°C and the supply water temperature is below 35°C.
A deviation alarm is given if the deviation is enough to cause an alarm (wee the previous set-
ting) and it lasts for the time period set here.
The controller gives a return water freezing risk alarm in addition to a lower and upper limit
alarm. The alarm limit for the freezing risk alarm is determined by the calculated return water
temperature (see p. 49).
A free lower limit temperature alarm that can be labelled.
A free upper limit temperature alarm that can be labelled.
0...95°C
0...95°C
0...95°C
0...95°C
0...95°C
0...95°C
0...95°C
1...20°C
0...120min
0...95°C
0...95°C
0...95°C
0...95°C
0...95°C
0...95°C
0...95°C
0...95°C
8.0°C
5.0°C
35°C
8°C
5°C
90°C
50°C
Not in use
60min
4°C
95°C
40°C
95°C
40°C
95°C
5°C
95°C
Room temperature
lower limit alarm,
freezing risk alarm
upper limit alarm
Supply water
lower limit alarm,
freezing risk alarm
upper limit alarm (radiator)
upper limit alarm (floor h.)
Supply water
deviation alarm
Delay of supply w.
deviation alarm
Return water lower
and upper limit alarm
Boiler’s lower
and upper limit alarm
Accumulator’s lower
and upper limit alarm
Measurem. 3 (4) lower-
and upper limit alarm
Alarm limits
The setting appears
if measurement 3
or 4 is reserved for
this purpose. The
alarm has a 5 se-
cond alarm delay.
Alarms
Alarms have a 5 second
alarm delay.
Alarms
Alarms
Alarm limits
Active alarms 3
Inactive alarms
Empty alarm log
You can set alarm limits from the controller’s alarm menu. Turn the control knob so the num-
ber is outside of the setting range to take the alarm out of use. The text “Not in use“ will
appear on the display. From the controller’s alarm menu you can check the controller’s ac-
tive alarms and what alarms have been active. If the controller has active alarms, the num-
ber of active alarms will appear in the main alarm menu.