23
Device settings: Measurement channel settings
The EH -800 controller has 4 measurement channels. If an extensi-
on unit EXU-800 is connected to the controller, the controller has 6
measurement channels.
Measurement channel 1 is reserved for outdoor temperature me-
asurement. The controller has its own plug-in for an outdoor tem-
perature sensor. If the controller is used as a constant temperature
controller, the outdoor temperature measurement can be activated
or inactivated at this point.
An H1 supply water sensor is already connected to measurement
channel 2.
Measurement channels 3 and 4 are connected to the controller using
a connecting cord. Select the use for the measurement channels at
this point. You can select a measurement connected to room com-
pensation, a factory set temperature measurement or different alarm
uses (contact information) as well as home/away switch use. “Me-
asurement 3”, “Measurement 4” and ”Alarm” can be freely labelled
according to their use.
Measurements 5 and 6 can be taken into use if an extension unit
EXU-800 has been connected to the controller.
Trend sampling interval
: Here you can set trend sampling interval
that is common for all measurements (see p. 7).
1. Move to Device settings and press OK.
2. You can see from the display if measurement channels have been
taken into use. Press OK.
Example 2. Measurement 4 for alarm use
1.
1. The most common alarms have already been programmed into
the controller. Select “Alarm” to use alarms that can be freely la-
belled.
2. Give the alarm a descriptive label. Use the control knob to select
a letter and press OK to confirm. When the label is ready, press
OK for a number of seconds.
3. Select either an opening or closing alarm. Exit with ESC.
Device settings-> Measurement channel settings
Example: Measurement 3 for room temperature measurement
Device settings
Language/Kieli/Språk...
English >
Measur. channel settings
>
H1 Process settings
>
H2 Process settings
>
2.
Device settings ... Measurements
Measurement 1
Outdoor temperature
Measurement 2 H1 Supply water
Measurement 3
Not in use >
Measurement 4
Not in use >
Measurement 5 Not in use >
Measurement 6
Not in use >
Trend sampling interval 600 s >
3.
Measurement 3
Not in use
H1 Room measurem. TMR
H1 Room temp. measurem. TMR / SP
Return water temperature
Temperature of accumulator
Temperature of boiler
Measurement 3
4.
Measurements
Measurement 3
H1 Room measurement TMR >
Measurement 4
Not in use >
Measurement 4
Not in use
H1 Room temp. potentiometer TMR / SP
Home/Away -switch
Return water temperature
H1 Room compensation TMR / P
Accumulator temp.
Boiler temp.
Solar collector
Measurement 4
Pressure alarm
Burner alarm
Pump alarm
Kattilahälytys
Boiler alarm
Alarm
Device settings..Measurements
Measurement 3
Not in use >
Measurement 4
Alarm >
Active state of alarm
Switch open >
Name of alarm
Alarm >
3. Select the measurement channel use. (additional information
about uses on the next page). Press OK.
4. Measurement channel 3 is now being used for room temperatu-
re measurement.