OPERATION SETTINGS
OI-6000-X-X-X-X-O OPS_GUIDE_REV 3.1
47
4.3.4
SENSOR HIGH ALARM RISE/FALL SETTING
1.
Use the ADD and SUB buttons to select between activation on a Rising or a Falling gas level,
respectively.
2.
Press the MENU button to save the desired setting and to advance to setting the radio address (if
you have a radio module installed), otherwise you will return to Normal Operating Mode.
NOTICE
The alarms will NOT activate, even in the presence of gas, until you have exited the menu mode for
approximately 1 minute.
For non-latching alarms, the alarms will NOT deactivate until the gas level reading at the sensor has fallen
10% below the alarm set-point.
4.4
SENSOR RADIO ADDRESS
The OI-6000 radio address is adjustable from 1 to 255, each sensor assembly on the network needs a unique radio
address in order to avoid a fault at the receiving monitor. The default radio address is 1.
1.
Use the ADD and SUB buttons to increase and decrease the sensor radio address, respectively.
2.
Press the MENU button to save the desired setting and to exit the operation settings menu, and to
return the device to normal operating mode.