INSTALLATION AND STARTUP
OI-6000-X-X-X-X-O OPS_GUIDE_REV 3.1
21
2.3.6
CONNECTING THE FAULT TERMINAL
The fault terminal is used to provide indication of a device failure. The fault terminal is a normally-closed
(NC), or fail-safe, configuration, terminating power to the external fault device when prompted. Unlike
the optional relay terminals, the fault terminal is a wet-contact, requiring only the power and ground wires
of the external fault device to be wired during installation. Refer to the following instructions for how to
wire your device:
On the external fault device (light/horn):
1.
Locate the power (RED) and ground (BLACK) wires on the alarming device.
On the GEN II Model OI-6000 Detector:
1.
Feed the alarming device wires through the power hub and into the enclosure.
2.
Locate the fault terminal block on the control board and complete the following:
a.
Connect the external fault device power (RED) wire to the “+” terminal.
b.
Connect the external fault device ground (BLACK) wire to the “-” terminal.
EXTERNAL
FAULT DEVICE
OI-6000
FAULT TERMINAL
PWR/+
RED
+
RED
GND/-
BLACK
-
BLACK