Details of command
−41−
Write parameters and operation data (remote register)
1)
Specify the register address number.
2)
Check the register address number response.
3) Turn the TRIG from OFF to ON. The selected parameter or operation data is started writing.
4) After checking the TRIG_R was turned from OFF to ON, check the command code response and DATA
response.
5) Turn the TRIG from ON to OFF, and check that the TRIG_R was turned from ON to OFF.
When writing 1000 to the "position" of the operation data No.0
TRIG
0001h
0001h
0 s or more
0 s or more
0 s or more
(TM+TS)×2
(TM+TS)×2
(TM+TS)×2
1200h
1000 (03E8h)
1200h
1000 (03E8h)
OFF
ON
TRIG_R
OFF
ON
DATA
DATA response
Command code
Register address number
response
Command code response
Register address number
[
NETC01-M3
to master]
[Master to
NETC01-M3
]