background image

20

AIM-OM-ATX-3, Rev. 2.1, 05/15

    •    Copyright Orenco Systems

®

, Inc. Property of Orenco Systems

®

, Inc. Do not reproduce or distribute without written authorization from Orenco: 800-348-9843.

AdvanTex

® 

O

&

M

 MANUAL

C O M M E R C I A L   T R E A T M E N T   S Y S T E M S

Maintenance (continued)

Corrective Maintenance

An alarm is triggered when the liquid in the tank reaches a level that 
is either higher or lower than it should be, under normal operating 
conditions. 

When responding to an alarm, first discern the type of alarm being 
activated. If it is due to pump failure, test each pump manually and locate 
the failed pump. To replace the pump, see the “Removing & Replacing 
Inoperative Pumps” section of this document. Remove the access riser lid 
and visually inspect the liquid level. If a high liquid level or low liquid level 
has caused the alarm, follow the appropriate procedures below. 

High Liquid Level Alarm

1. Determine if the high water alarm is from higher than expected 

usage (i.e., special event, etc.). If there is a long-term increase in 
flows, then timer settings need to be adjusted accordingly.

2. When a high liquid level condition exists, the source of the problem is 

likely to be one of the following:

a. Poor valve seal – Consult the design plans for proper operating 

level and visually inspect the recirculating valve to verify the liquid 
level in the tank is within the normal range. If the liquid level is 
high, the valve may require cleaning because it is not making a 
tight seal when seated. Remove, disassemble, and inspect.

b. Control panel breakers tripped – Check the circuit breakers, 

switches, and fuses in the system control panel. If separate 
breakers in the main panel were used for the pumps and controls, 
also check these breakers. If a breaker is found to be tripped, 
reset the breaker. If the breaker trips immediately, check the 
wiring for a short or bad breaker. If the breaker or breakers don’t 
trip again, then the problem has probably been found or has 
corrected itself. Test the automatic function of the system as 
shown in the “Start-up & Operation” section of this manual to 
verify proper operation.

c. Faulty floats – If, after checking the circuit breakers, fuses, and 

switches, the pump still does not operate, toggle the “AUTO-
OFF-MAN” switch to “MAN.” If the pump engages, the problem 
is likely to be in the float system. (If the motor contactor engages 
but the pump doesn’t run, go to step g, “Water in splice box or 
loose wires.”) Pump the tank down to a level below the “Override 
Timer On/Off” float. Cycle the pump to simulate the timer on 
and off periods so the effluent is dosed to different zones of 
the AdvanTex

®

 system. Toggle the “AUTO-OFF-MAN” switch to 

“AUTO.” Do not leave a pump in the “MAN” position unattended. If 
you do, the pump can continue to operate without liquid, possibly 
drawing solids into the filter and causing potential failures. Isolate 
the float switches and check to ensure all floats are operating 
properly. If a float is found to be faulty, refer to the “Removing & 
Replacing Inoperative Floats” section in this document.

 

IMPORTANT!

 

Before doing any work on either the wiring to 

the level control floats and pump or inside the pump control 
panel, switch off the power to the system at the service 
entrance panel and set the circuit breakers in the panel to 
their “OFF” positions.

d. Pump clogged or not clean – Check the pump for discharge 

flow. Close the ball valve, disconnect the union in the discharge 
plumbing assembly and turn the union so it is facing down. 
Engage the pump and visually inspect the approximate flow 
rate being discharged. If you are unsure of the discharge rate, 
measure the time it takes to fill a five-gallon bucket with the 
discharge. Check this value against the appropriate pump curve. 
If the flow rate is insufficient, the pump may need to be cleaned. 
Refer to the 

Pump Repair Manual

 provided in Appendix D.

e. Valves closed – If the pump operates in the proper flow range, 

check all downstream valves to ensure that they are in the open 
position. If the valves are all open, test the discharge pressure of 
the pump. For proper pump testing methods, refer to the 

Pump 

Repair Manual

 provided in Appendix D.

Summary of Contents for AdvanTex AX100

Page 1: ...Start Up and Maintenance of AdvanTex AX100 AX20 Commercial Wastewater Treatment Systems AdvanTex O M MANUAL 800 348 9843 541 459 4449 www orenco com www vericomm net Orenco COMMERCIAL MANUAL O M...

Page 2: ...on and treatment is our only job When you purchase an Orenco system you can be confident you have chosen the best equipment available Assistance In addition to providing quality equipment Orenco pride...

Page 3: ...ints Recirculation Blend Tank 13 Inspection Points AdvanTex Filter Pods 13 Inspection Points Vent Fan Assembly 14 Inspection Points Distribution Valve 14 Housekeeping 14 Maintenance Tools Equipment an...

Page 4: ...ion from AdvanTex filtrate returning from the flow splitter basin The harmless nitrogen gas is released freely back into the atmosphere Recirculation Blend Tank The recirculation blend tank reduces th...

Page 5: ...nstallation of all equipment and the availability of power phone line and water at the site The AdvanTex Dealer is expected to be on site and is either performing the start up or acting as a coordinat...

Page 6: ...tion Site drainage Verify that all riser lids external splice box lids and AX pod lids are level and above grade Serviceability Verify that there is a minimum of two feet of space between AX pods Chec...

Page 7: ...control panel to assure proper system operation and component longevity 4 Power supply voltage Make sure the panel breakers are switched off and check the power supply voltage at the panel On 120 V pa...

Page 8: ...er Inspect the riser attachment and rubber grommets for a watertight seal 4 Splice box Inspect the splice box for correct wiring and the use of waterproof splice nuts If there is water in the splice b...

Page 9: ...TCOM control panels d Check the float settings provided in the plans against the actual float settings If the plans don t provide float settings and the engineer or system designer is unable to provi...

Page 10: ...r cam lock fitting and open the discharge assembly ball valve i Switch the pump breaker s in the control panel to the ON position when finished Inspection Points Pumps When the panel has been inspecte...

Page 11: ...3200 3 5 3 9 PF500512 5 4 6 2 PF100552 3 6 3 8 PF500532 2 6 3 0 PF100712 7 8 8 4 PF50053200 3 2 3 7 PF10073200 4 9 5 2 PF500534 1 3 1 5 PF100752 5 8 6 2 PF500552 3 3 3 9 PF101012 9 0 9 8 PF500712 7 3...

Page 12: ...ur system before testing d Lower the float assembly into the tank and clip the float assembly into the float bracket Timed dose a Toggle the AUTO OFF MAN switch to the AUTO position b Record the timer...

Page 13: ...of 9 inches 229 mm from the normal liquid level to the RO float Inspection Points AdvanTex Filter Pods Your system may include AX100 filter pods shown or AX20 filter pods For AX20 inspection points se...

Page 14: ...location of all distribution valves in the system 1 Verify liquid level Make sure that the tank or basin that you are pumping from has sufficient liquid to perform the test WARNING There is no motor...

Page 15: ...r gloves Trash bags Routine Inspection and Maintenance Biotube filter cradle OM BIOTUBECRADLE Beakers or bottles Calculator Channel lock pliers Dissolved oxygen DO meter or colorimetric ampoules 3 16...

Page 16: ...istribute upon request To request multiple copies of this manual contact Orenco Systems Inc at 1 800 348 9843 With preventive maintenance and periodic inspections the wastewater treatment system will...

Page 17: ...r biological growth on the spray nozzles Observe and measure the residual pressure Refer back to the Start up Operation section for initial measurements of residual pressure If the observed residual p...

Page 18: ...E Turn the laterals in the AdvanTex treatment unit 180 degrees so the spray nozzle turbines face up prior to flushing to prevent nozzle clogging while material is being pushed along the lateral to the...

Page 19: ...Recommended Activity Period Activity Visual Inspection of Tank Liquid Levels 1 Check Biotube Effluent Filters Clean as Required 1 Check Biotube Pump Vault Filters Clean as Required 1 Record Elapsed Ti...

Page 20: ...itself Test the automatic function of the system as shown in the Start up Operation section of this manual to verify proper operation c Faulty floats If after checking the circuit breakers fuses and...

Page 21: ...umping downhill A system will not necessarily siphon every time it operates It is dependent on the system design A siphoning system can be retrofitted with an anti siphon valve Most siphoning problems...

Page 22: ...he splice box lid being careful not to drop the screws into the tank If the splice box was submerged or if there is a crack in the conduit there may be water in the splice box If this is the case remo...

Page 23: ...______________________ __________________________________________________ __________________________________________________ __________________________________________________ ________________________...

Page 24: ...________ __________________________________________________ __________________________________________________ __________________________________________________ ______________________________________...

Reviews: