19
Copyright Orenco Systems
®
, Inc. Property of Orenco Systems
®
, Inc. Do not reproduce or distribute without written authorization from Orenco: 800-348-9843. •
AIM-OM-ATX-3, Rev. 2.1, 05/15
AdvanTex
®
O
&
M
MANUAL
C O M M E R C I A L T R E A T M E N T S Y S T E M S
Scheduled Maintenance Reference Chart
NOTE:
All designer specifications and local regulatory requirements
should be followed. This table provides Orenco’s minimum recommended
guidelines.
Maintenance (continued)
1
This maintenance schedule is only required during the first year of system operation.
2
Recommended guidelines only. Sampling should be scheduled according to regulatory requirements.
Scheduled Maintenance Reference Chart
Recommended Activity Period
Activity
Visual Inspection of Tank Liquid Levels
•
1
•
Check Biotube
®
Effluent Filters; Clean as Required
•
1
•
Check Biotube
®
Pump Vault Filters; Clean as Required
•
1
•
Record Elapsed Time Meters and Event Counters for All Pumps
•
Confirm Proper Operation of Automatic Distributing Valve (if applicable)
•
Sample Influent and Effluent Quality Parameters
2
•
1
•
Confirm and Record Pump Voltages and Amperages
•
1
•
Inspect Distribution of Effluent in AdvanTex Pods; Clean as Required
•
Measure Inlet or Residual Pressures to AdvanTex Pods; Clean as Required
•
Inspect Recirculating Valve
•
Record Scum and Sludge Accumulation in Tanks
•
Flush Distribution Laterals in AdvanTex Pods
•
Inspect Pumping System Components; Clean as Required
•
Replace Lithium Battery in TCOM Control Panel (if applicable)
•
Monthly
Quarterly Semi-annuallyAnnually Biannually