background image

12

AIM-OM-ATX-3, Rev. 2.1, 05/15

    •    Copyright Orenco Systems

®

, Inc. Property of Orenco Systems

®

, Inc. Do not reproduce or distribute without written authorization from Orenco: 800-348-9843.

AdvanTex

® 

O

&

M

 MANUAL

C O M M E R C I A L   T R E A T M E N T   S Y S T E M S

2. 

Drawdown test: 

Perform a drawdown test to set the pump flow 

rate in the control panel.

  a. Measure and record the distance from the top of the tank to the 

liquid level in the tank.

  b. Toggle the pump “AUTO-OFF-MAN” switch to the “MAN” position 

for sixty seconds.

  c. Toggle the pump “AUTO-OFF-MAN” switch to the “OFF” position; 

then measure and compare the difference in elevations. The 
difference in elevation in inches or millimeters, multiplied by the 
gallons per inch or liters per millimeter of the tank or basin will 
provide the correct flow rate in gallons per minute (gpm) or liters 
per minute (L/min). Follow the instructions provided with the control 
panel for entering the measured pump flow rate.

 NOTE: 

This method will not work on recirculation/blend tanks if 

the flow is returning to the tank through the recirc valve or for 
dose tanks with transport lines that drain back.

3. 

Automatic pump operation: 

Test the system using the floats to 

drive pump operation. 
•  Demand dose:

a. Toggle the “AUTO-OFF-MAN” switch to the “AUTO” position. 

b. Unclip the float assembly and remove it from the tank if it is not 

out already.

c. Verify the automatic operation of the pumps by incrementally 

lifting the floats to simulate normal raising and lowering of the 
tank liquid level. The pumps should cycle on when you lift them 
and cycle off when you release them. On duplex systems, the 
pumps should alternate between lead and lag pumps and cycle 
off when the floats are dropped. 

 

NOTE:

 An “On/Off” float works differently than a pair of “On” and 

“Off” floats. Verify the type of floats in your system before testing.

d. Lower the float assembly into the tank and clip the float 

assembly into the float bracket.

•  Timed dose: 

a. Toggle the “AUTO-OFF-MAN” switch to the “AUTO” position.

b. Record the timer settings, then reduce the timer settings to 0.5 

minutes “OFF,” 0.5 minutes “ON,” and 1.0 minutes “OVR OFF.”

c. Let the pump run through several cycles to confirm that the 

timers are operating correctly. 

d. Change the timer settings back to the settings specified by the 

engineer.

Inspection Points – 

System Timer Settings

1.

 Recirc Timer Settings: 

The method for calculating Recirculation/

Blend Tank timer settings is provided below. Newer AX100 panels 
have the ability to adjust the timer setting based on actual flow 
data. See the instructions included with the control panel for setting 
information.

•  Pump On Time = 1.5 Minutes 

NOTE:

 The standard Pump On Time for AX100 units is 1.5 

minutes. Your system’s needs may differ. Consult your site 
plans, engineer/designer, or Orenco for more details.

•  Pump Off time = (1440 ÷ Cycles per Day) - Pump On Time

Calculate Cycles per Day using the equation below:

NOTES:

  

- 1440 is the number of available minutes in a 24-hour period. 
- The standard Recirc Ratio for AX100 units is 4 but it can  
  range from 2 to 6, depending on the needs of the system.  
- The Pump Flow Rate is 48 gallons per minute (3 L/sec) when  
  nozzle pressure measures 3.0 psi (20.6 kPa).

2.

 Discharge Timer Settings (Timed Dose Systems) : 

The timer 

settings for the system are calculated based on the actual and 
expected flow. Equations are provided below.

  a. Identify Dose Volume

•  Dose Volume = Number of gallons desired per dose  

or 

•  Dose Volume = (Number of Orifices) × (Loading Rate per Orifice)

  b. Identify Doses per Day

•  Number of doses per day = (Design Flow) ÷ (Dose Volume)

  c. Identify Time Interval Between Starts, in hours

•  Time Interval Between Starts = (Hours per Day) ÷ (Doses per Day)

  d. Identify Time On, in minutes 

•  Time On = (Dose Volume) ÷ (Measured Pump gpm)

Inspection Points (continued)

(Average Daily Flow) × (Recirc Ratio)

(Pump Flow Rate) × (Pumps per Dose) × (Pump On Time) 

Summary of Contents for AdvanTex AX100

Page 1: ...Start Up and Maintenance of AdvanTex AX100 AX20 Commercial Wastewater Treatment Systems AdvanTex O M MANUAL 800 348 9843 541 459 4449 www orenco com www vericomm net Orenco COMMERCIAL MANUAL O M...

Page 2: ...on and treatment is our only job When you purchase an Orenco system you can be confident you have chosen the best equipment available Assistance In addition to providing quality equipment Orenco pride...

Page 3: ...ints Recirculation Blend Tank 13 Inspection Points AdvanTex Filter Pods 13 Inspection Points Vent Fan Assembly 14 Inspection Points Distribution Valve 14 Housekeeping 14 Maintenance Tools Equipment an...

Page 4: ...ion from AdvanTex filtrate returning from the flow splitter basin The harmless nitrogen gas is released freely back into the atmosphere Recirculation Blend Tank The recirculation blend tank reduces th...

Page 5: ...nstallation of all equipment and the availability of power phone line and water at the site The AdvanTex Dealer is expected to be on site and is either performing the start up or acting as a coordinat...

Page 6: ...tion Site drainage Verify that all riser lids external splice box lids and AX pod lids are level and above grade Serviceability Verify that there is a minimum of two feet of space between AX pods Chec...

Page 7: ...control panel to assure proper system operation and component longevity 4 Power supply voltage Make sure the panel breakers are switched off and check the power supply voltage at the panel On 120 V pa...

Page 8: ...er Inspect the riser attachment and rubber grommets for a watertight seal 4 Splice box Inspect the splice box for correct wiring and the use of waterproof splice nuts If there is water in the splice b...

Page 9: ...TCOM control panels d Check the float settings provided in the plans against the actual float settings If the plans don t provide float settings and the engineer or system designer is unable to provi...

Page 10: ...r cam lock fitting and open the discharge assembly ball valve i Switch the pump breaker s in the control panel to the ON position when finished Inspection Points Pumps When the panel has been inspecte...

Page 11: ...3200 3 5 3 9 PF500512 5 4 6 2 PF100552 3 6 3 8 PF500532 2 6 3 0 PF100712 7 8 8 4 PF50053200 3 2 3 7 PF10073200 4 9 5 2 PF500534 1 3 1 5 PF100752 5 8 6 2 PF500552 3 3 3 9 PF101012 9 0 9 8 PF500712 7 3...

Page 12: ...ur system before testing d Lower the float assembly into the tank and clip the float assembly into the float bracket Timed dose a Toggle the AUTO OFF MAN switch to the AUTO position b Record the timer...

Page 13: ...of 9 inches 229 mm from the normal liquid level to the RO float Inspection Points AdvanTex Filter Pods Your system may include AX100 filter pods shown or AX20 filter pods For AX20 inspection points se...

Page 14: ...location of all distribution valves in the system 1 Verify liquid level Make sure that the tank or basin that you are pumping from has sufficient liquid to perform the test WARNING There is no motor...

Page 15: ...r gloves Trash bags Routine Inspection and Maintenance Biotube filter cradle OM BIOTUBECRADLE Beakers or bottles Calculator Channel lock pliers Dissolved oxygen DO meter or colorimetric ampoules 3 16...

Page 16: ...istribute upon request To request multiple copies of this manual contact Orenco Systems Inc at 1 800 348 9843 With preventive maintenance and periodic inspections the wastewater treatment system will...

Page 17: ...r biological growth on the spray nozzles Observe and measure the residual pressure Refer back to the Start up Operation section for initial measurements of residual pressure If the observed residual p...

Page 18: ...E Turn the laterals in the AdvanTex treatment unit 180 degrees so the spray nozzle turbines face up prior to flushing to prevent nozzle clogging while material is being pushed along the lateral to the...

Page 19: ...Recommended Activity Period Activity Visual Inspection of Tank Liquid Levels 1 Check Biotube Effluent Filters Clean as Required 1 Check Biotube Pump Vault Filters Clean as Required 1 Record Elapsed Ti...

Page 20: ...itself Test the automatic function of the system as shown in the Start up Operation section of this manual to verify proper operation c Faulty floats If after checking the circuit breakers fuses and...

Page 21: ...umping downhill A system will not necessarily siphon every time it operates It is dependent on the system design A siphoning system can be retrofitted with an anti siphon valve Most siphoning problems...

Page 22: ...he splice box lid being careful not to drop the screws into the tank If the splice box was submerged or if there is a crack in the conduit there may be water in the splice box If this is the case remo...

Page 23: ...______________________ __________________________________________________ __________________________________________________ __________________________________________________ ________________________...

Page 24: ...________ __________________________________________________ __________________________________________________ __________________________________________________ ______________________________________...

Reviews: