Detecting and Managing Faults
21
■
“Voltage Out of Range” on page 22
Related Information
■
“Display Oracle ILOM Sensor Status” on page 18
■
“Determine Oracle ILOM Sensor Target Types” on page 20
■
“Evaluating a Temperature Sensor Alarm” on page 23
■
“Evaluating a Speed Sensor Alarm” on page 26
■
“Evaluating a State Sensor Alarm” on page 29
■
“Evaluating a Presence Sensor Alarm” on page 30
■
“Evaluating an Indicator State” on page 32
▼
Evaluate a Voltage Sensor
1. Display the sensor status and determine the target type.
See:
■
“Display Oracle ILOM Sensor Status” on page 18
■
“Determine Oracle ILOM Sensor Target Types” on page 20
2. Compare the displayed value with a known good range.
See
“Voltage Sensor Values” on page 22
.
3. Learn why a voltage sensor might alarm.
See
“Voltage Out of Range” on page 22
.
4. Determine your next step.
Related Information
■
“Voltage Sensor Values” on page 22
■
“Voltage Out of Range” on page 22
Voltage Sensor Target
Action
Links
•
/SYS/MB/V_3.3VMain
•
/SYS/MB/V_3.3VStby
•
/SYS/MB/V_12V
Replace the power supply.
“Servicing Power Supplies”
on page 41
/SYS/MB/V_BAT
Replace the battery.
“Servicing the Battery” on
page 75
All other voltage sensor
targets.
Replace the gateway.
“Remove the Gateway From
the Rack” on page 77