Install a Power Supply
You will hear an audible click when the power supply is fully seated.
4.
Reconnect the power cord to the power supply.
5.
If you disconnected the two CMA left-side connectors, reconnect the CMA.
For instructions on reconnecting the CMA see
“Attach the CMA to the Server” in
.
6.
Verify that the AC OK LED is lit.
“Locate a Faulty Power Supply” on page 77
7.
Verify that the following LEDs are not lit:
■
Service Required LED on the power supply
■
Front and rear Service Required LEDs
■
Rear PS Failure LED on the bezel of the server
“Interpreting LEDs” on page 27
8.
“Verify a Power Supply” on page 82
Servicing Power Supplies
81