SECTION 2
Installation and Connections/Wiring
Installation
CIDRW Controller
There is a switch for selecting the operation mode (Normal Operation mode <-> Setting mode) on the bottom face of the
CIDRW Controller. Set the communications conditions in the Setting mode (switch position 3) before mounting the
CIDRW Controller.
Set the Controller to the Normal Operation mode (switch position 0) when mounting it.
Mount the CIDRW Controller with the resin washers and four M4 screws provided as accessories.
•
Tighten the M4 screws with a torque not exceeding 1.2 N·m.
•
Do not apply organic solvents used with screw locking agents at the locations where the screws are inserted.
130±0.2
151±0.2
4-M4
Mounting dimensions
(Unit: mm)