6-5
Section
System
148
Item
Setting
Baud rate
38400 (bps)
Data length
8 (bit)
Parity bits
None
Stop bits
1 (bit)
Footer
CR
3
Start the Hyper Terminal program on the computer and
make the following communication settings.
The same communication settings must be used on both
the V530-R150 and the modem on the computer.
Item
Setting
Baud rate (B)
38400 (bps)
Data length (D)
8 (bit)
Parity bits
None
Stop bits
1 (bit)
Flow control
None (XMODEM protocol is used.)
4
Save data from the V530-R150.
The data transfer screen will be displayed.
Saving Data
5
Select
Transfer/Receive File from the Hyper Terminal
menu.
•
Specify where the file is to be saved.
•
Set the protocol to
Xmodem.
6
Select
Receive and input the file name.
The data will be transferred from the V530-R150 to the com-
puter.
The V530-R150 generates a timeout error if no response is
received from the external device within 30 seconds. An er-
ror message will be displayed, and the error terminal will
turn ON.
Loading Data From the Computer (V530-R150
←
Personal Computer)
Procedure
1
Follow steps 1 to 3 in the above procedure to connect the
V530-R150 and the computer.
2
Select
Transfer/Send File from the Hyper Terminal menu.
•
Select the file to be loaded.
•
Set the protocol to
Xmodem.