141
Programming Console Operations
Section 7-2
Word Monitor
Follow the procedure below to monitor the status of a particular word.
1,2,3...
1.
Press the CLR Key to bring up the initial display.
2.
Input the word address of the desired word.
3.
Press the MONTR Key to begin monitoring.
The Up or Down Arrow Key can be pressed to display the status of the pre-
vious or next word.
The displayed word’s status can be changed using the Hexadecimal/BCD
Data Modification operation. Refer to Refer to 7-2-22 Hexadecimal, BCD
Data Modification, 7-2-23 Binary Data Modification, 7-2-24 Signed Deci-
mal Data Modification, and 7-2-25 Unsigned Decimal Data Modification for
details.
4.
Press the CLR Key to end monitoring.
Note The operating mode can be changed without altering the current monitor dis-
play by holding down the SHIFT Key and then changing the operating mode.
Multiple Address
Monitoring
The status of up to six bits and words can be monitored simultaneously,
although only three can be shown on the display at any one time.
1,2,3...
1.
Press the CLR Key to bring up the initial display.
2.
Input the address of the first bit or word and press the MONTR Key.
3.
Repeat step 2 up to 6 times to display the next addresses to be monitored.
If 4 or more bits and words are being monitored, the bits and words that do
not appear on the display can be displayed by pressing the MONTR Key.
If the MONTR Key is pressed alone, the display will shift to the right.
If more than six bits and words are input, monitoring of the bit or word input
first will be canceled.
4.
Press the CLR Key to stop monitoring the leftmost bit or word and clear it
from the display.
5.
Press the SHIFT and CLR Keys to end monitoring altogether.
SHIFT
CH
*DM
LR
*EM
B
1
00000
CHANNEL LR 01
MONTR
cL01
FFFF
CLR
00000
CHANNEL LR 01
TIM
MONTR
T000
0100
SHIFT
CONT
#
B
1
MONTR
00001 T000
^ OFF 0100
DM
EM
MONTR
D000000001 T000
0000^ OFF 0100
CLR
00001 T000
^ OFF 0100
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com