98
Specifications and Part Names
Section 6-2
Analog Input Signal Ranges
–10 to 10 V
The voltage range –10 to 10 V corresponds to hexadecimal values F448 to
0BB8 (–3,000 to 3,300 decimal). Negative voltages are expressed as two’s
complements.
0 to 10 V
The voltage range 0 to 10 V corresponds to hexadecimal values 0000 to 1770
(0 to 6,000 decimal). The range of data that can be converted is FED4 to
189C (–300 to 6,300 decimal). Negative voltages are expressed as two’s
complements.
0CE4 (3,300)
0BB8 (3,000)
Conversion data
Hexadecimal (decimal)
−
11 V
−
10 V 0000 (0)
0 V
10 V 11 V
F448 (
−
3,000)
F31C (
−
3,300)
Conversion data
Hexadecimal (decimal)
189C (6,300)
1770 (6,000)
−
0.5 V
0000 (0)
0 V
10 V 10.5 V
FED4 (
−
300)