![background image](http://html1.mh-extra.com/html/omron/sysmac-c200h-asc02/sysmac-c200h-asc02_operation-manual_742429138.webp)
Appendix D
Formatting and Data Conversion
133
Execution Times
Command
Execution time (ms)
PC READ “ I 4 ” ; A
8.5
PC READ “ 5 I 4 ” ; A, B, C, D, E
21.1
PC READ “ 1 0 I 4 ” ; A, B, C, D, E, G, H, I, J
43.8
PC READ “ 1 0 0 A 3, 1 0 0 A 3, 5 5 A 3 ” ; A $, B $, C $
67.7
PC WRITE “ I 4 ” ; A
8.7
PC WRITE “ 5 I 4 ” ; A, B, C, D, E
22.1
PC WRITE “ 1 0 I 4 ” ; A, B, C, D, E, G, H, I, J
39.3
PC WRITE “ 1 0 0 A 3, 1 0 0 A 3, 5 5 A 3 ” ; A $, B $, C $
57.9
PC READ “ @ D, 0, 1, I 4 ” ; A
5.0
PC READ “ @ D, 0, 5, 5 I 4 ” ; A, B, C, D, E
18.6
PC READ “ @ D, 0, 10, 1 0 I 4 ” ; A, B, C, D, E, G, H, I, J
40.3
PC READ “ @ D , 0, 2 5 5, 1 0 0 A 3, 1 0 0 A 3, 5 5 A 3 ” ; A $, B $, C $
65.3
PC WRITE “ @ D, 0, 1, I 4 ” ; A
4.4
PC WRITE “ @ D, 0, 5, 5 I 4 ” ; A, B, C, D, E
19.0
PC WRITE “ @ D, 0, 10, 1 0 I 4 ” ; A, B, C, D, E, G, H, I, J
37.5
PC WRITE “ @ D , 0, 2 5 5, 1 0 0 A 3, 1 0 0 A 3, 5 5 A 3 ” ; A $, B $, C $
54.4
Remarks:
The execution times listed in this table do not include the time required for handshaking. The actual execution
time varies depending on the scan time of the PC as follows:
Twenty or fewer words are to be transferred:
•
without memory area designator: 2 PC scan times max.
•
with memory area designator: 1 PC scan time max.
More than 20 words are to be transferred:
•
without memory area designator: INT(No. of words -1)/20)+2 scan times max.
•
with memory area designator: INT(No. of words -1)/20)+1 scan time max.
Summary of Contents for SYSMAC C200H-ASC02
Page 1: ...Cat No W165 E1 04 ASCII Unit SYSMAC C200H ASC02 ...
Page 2: ...C200H ASC02 ASCII Unit Operation Manual Revised September 2002 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 7: ...TABLE OF CONTENTS viii Glossary 159 Index 163 Revision History 165 ...
Page 122: ...Appendix B Specifications 115 130 35 100 5 ...
Page 168: ...Cat No W165 E1 04 C200H ASC02 ASCII Unit OPERATION MANUAL ...