Setting the Acceleration/Deceleration Time
The following description provides information on parameters related to acceleration
and deceleration time settings.
Trapezoidal and S-shape acceleration and deceleration are available. Using the S-
shape characteristic function for acceleration and deceleration can reduce shock to the
machinery when stopping or starting.
H
Setting the Acceleration/Deceleration Time (n16 through n19)
•
Two acceleration times and two deceleration times can be set.
•
The acceleration time is the time required to go from 0% to 100% of the maximum frequency and the
deceleration time is the time required to go from 100% to 0% of the maximum frequency. The actual
acceleration or deceleration time is obtained from the following formula.
Acceleration/Deceleration time = (Acceleration/Deceleration time set value)
×
(Frequency reference value)
÷
(Max. frequency)
Acceleration time 2 and deceleration time 2 are enabled by setting 11 for acceleration/deceleration time
selection in any of the n36 through n39 parameters for multi-function input.
Deceleration time 2 is also enabled by emergency-stop settings 19, 20, 21, and 22 in any of the n36,
n37, n38, and n39 parameters for multi-function input with n04 for interruption mode selection set to 0
(i.e., deceleration stop).
n16
Acceleration time 1
Changes during
operation
Yes
Setting
range
0.0 to 999 (s)
Unit of
setting
0.1 s
(see note)
Default setting
10.0
n17
Deceleration Time 1
Changes during
operation
Yes
Setting
range
0.0 to 999 (s)
Unit of
setting
0.1 s
(see note)
Default setting
10.0
n18
Acceleration Time 2
Changes during
operation
Yes
Setting
range
0.0 to 999 (s)
Unit of
setting
0.1 s
(see note)
Default setting
10.0
n19
Deceleration Time 2
Changes during
operation
Yes
Unit of
setting
0.0 to 999 (s)
Unit of
setting
0.1 s
(see note)
Default setting
10.0
Note
Values will be set in 0.1-Hz increments if the frequency is less than 100 Hz and 1-Hz increments if
the frequency is 100 Hz or over.
Basic Operation
Chapter 5
Summary of Contents for SYSDRIVE 3G3JV-A4002
Page 1: ...USER S MANUAL SYSDRIVE 3G3JV Compact Simplified Inverters Cat No I528 E1 04...
Page 3: ...USER S MANUAL Compact Simplified Inverter SYSDRIVE 3G3JVSERIES...
Page 16: ......
Page 20: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 26: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 57: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 65: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 216: ...Chapter 10 List of Parameters 10...
Page 229: ...Chapter 11 Using the Inverter for a Motor 11...