7-18
7-4-3 Loop-back Test (Function Code: 08 Hex)
H
Settings and Response
•
The DSR message from the Master is returned as a response. The Inverter does not retrieve or pro-
cess this data.
•
The DSR message or normal response for loop-back test use is divided into 8-byte blocks as shown
below. Any data can be set as test data 1 or 2 provided that the number of data items remains changed.
•
This command is used for checking the status of communications or for dummy communications with-
out detecting any communications time-over.
D
DSR Message
Byte No.
Data
1
Slave address
2
Function code (08 Hex)
3
Test data 1
4
5
Test data 2
6
7
CRC-16 check
8
D
Response
Normal
Byte No.
Data
1
Slave address
2
Function code (08 Hex)
3
Test data 1
4
5
Test data 2
6
7
CRC-16 check
8
Error
Byte No.
Data
1
Slave address
2
Function code (88 Hex)
3
Error code
4
CRC-16 check
5
Note
When an error occurs, the MSB of the function code will be set to 1.
Communications
Chapter 7
Summary of Contents for SYSDRIVE 3G3JV-A4002
Page 1: ...USER S MANUAL SYSDRIVE 3G3JV Compact Simplified Inverters Cat No I528 E1 04...
Page 3: ...USER S MANUAL Compact Simplified Inverter SYSDRIVE 3G3JVSERIES...
Page 16: ......
Page 20: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 26: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 57: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 65: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 216: ...Chapter 10 List of Parameters 10...
Page 229: ...Chapter 11 Using the Inverter for a Motor 11...