![Omron SYSDRIVE 3G3JV-A4002 User Manual Download Page 205](http://html1.mh-extra.com/html/omron/sysdrive-3g3jv-a4002/sysdrive-3g3jv-a4002_user-manual_742832205.webp)
9-16
9-2-11 AC Reactor
H
3G3IV-PUZBAB
j
(Yaskawa Electric)
The AC Reactor suppresses harmonic current generated from the Inverter and improves the power fac-
tor of the Inverter. Connect the AC Reactor to the Inverter if the capacity of the power supply is much
larger than that of the Inverter. Select the AC Reactor model from the following table according to the
motor capacity.
H
Connection Example
MCCB AC Reactor
Motor
H
Applicable Range
Power supply
capacity (kVA)
AC Reactor required
for smooth operation
under present power
supply conditions
AC Reactor
not required
Inverter capacity (kVA)
H
Applicable Models and Dimensions
D
200-V Class
Max. applicable
motor capacity (kW)
Model
3G3IV-
PUZBAB
j
Current (A)
Inductance
(mH)
Loss (W)
Weight (kg)
0.1 to 0.2
2A7.0MH
2
7.0
8
2.5
0.4
2.5A4.2MH
2.5
4.2
15
2.5
0.75
5A2.1MH
5
2.1
15
2.5
1.5
10A1.1MH
10
1.1
25
3
2.2
15A0.71MH
15
0.71
30
3
3.7
20A0.53MH
20
0.53
35
3
Specifications
Chapter 9
Summary of Contents for SYSDRIVE 3G3JV-A4002
Page 1: ...USER S MANUAL SYSDRIVE 3G3JV Compact Simplified Inverters Cat No I528 E1 04...
Page 3: ...USER S MANUAL Compact Simplified Inverter SYSDRIVE 3G3JVSERIES...
Page 16: ......
Page 20: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 26: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 57: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 65: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 216: ...Chapter 10 List of Parameters 10...
Page 229: ...Chapter 11 Using the Inverter for a Motor 11...