10-11
Parame-
ter No.
(Register
No.
(Hex))
Refer-
ence
page
Changes
during
operation
Default
setting
Unit of
setting
Setting
range
Description
Name
n60
(013C)
Overtorque
detection lev-
el
Used to set overtorque detection level.
Set the level in percentage based on the rated cur-
rent of the Inverter as 100%.
30 to
200
1%
160
No
6-9
n61
(013D)
Overtorque
detection time
Used to set the detection time of overtorque.
0.1 to
10.0
0.1 s
0.1
No
6-10
n62
(013E)
UP/DOWN
command fre-
quency
memory
Used to store the adjusted frequency reference with
the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or more.
Used to store the adjusted frequency reference with
the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or more.
Used to store the adjusted frequency reference with
the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or more.
0, 1
1
0
No
6-19
n63
(013F)
Torque com-
pensation
gain
Used to set the gain of the torque compensation
function.
The default setting does not need any changes in
normal operation.
0.0 to
2.5
0.1
1.0
Yes
6-11
n64
(0140)
Motor rated
slip
Used to set the rated slip value of the motor in use.
Note
Used as the constant of the slip compensation
function.
0.0 to
20.0
0.1 Hz
Varies
with the
capac-
ity.
Yes
6-12
n65
(0141)
Motor no-load
current
Used to set the no-load current of the motor in use
based on the rated motor current as 100%.
Note
Used as the constant of the slip compensation
function.
0 to 99
1%
Varies
with the
capac-
ity.
No
6-12
n66
(0142)
Slip com-
pensation
gain
Used to set the gain of the slip compensation func-
tion.
Note
The slip compensation function is disabled
with n66 set to 0.0.
0.0 to
2.5
0.1
0.0
Yes
6-12
n67
(0143)
Slip com-
pensation
time constant
Used for the response speed of the slip compensa-
tion function.
Note
The default setting does not need any
changes in normal operation.
0.0 to
25.5
0.1 s
2.0
No
6-12
n68
(0144)
(See note
3.)
RS-422A/485
communica-
tions time-
over detec-
tion selection
Used to set whether a communications time-over
(CE) is detected if there is an interval of more than 2
s, and to select the method of processing the
detected communications time-over.
0: Detects a time-over and fatal error and coasts to
a stop.
1: Detects a time-over and fatal error and deceler-
ates to a stop in deceleration time 1.
2: Detects a time-over and fatal error and deceler-
ates to a stop in deceleration time 2.
3: Detects a time-over and nonfatal error warning
and continues operating.
4: No time-over is detected.
0 to 4
1
0
No
7-5
List of Parameters
Chapter 10
Summary of Contents for SYSDRIVE 3G3JV-A4002
Page 1: ...USER S MANUAL SYSDRIVE 3G3JV Compact Simplified Inverters Cat No I528 E1 04...
Page 3: ...USER S MANUAL Compact Simplified Inverter SYSDRIVE 3G3JVSERIES...
Page 16: ......
Page 20: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 26: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 57: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 65: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 216: ...Chapter 10 List of Parameters 10...
Page 229: ...Chapter 11 Using the Inverter for a Motor 11...