A-3-9 NQ with Mitsubishi FRS Inverter and Mitsubishi FRS520E
To perform a successful communication proceed as follows.
1 Right-click the
Nodes
folder and click
Add...
.
2 Set all data as shown in the screen shot.
3 Create PLC tag with address
A000
(Run Command).
4 Add an
Advanced Bit Button
task with
Press
task:
• Write
2
to
A000
:
To run/start the drive frequency to Max Freq Defined
• Write
0
to
A000
:
To stop the inverter frequency to Min Freq 00.0
5 Create PLC tag with address
M000
(Link Parameter Exp) and
C000
(Operation Mode).
6 Create PLC tag with address
D000
(Output Frequency).
7 Add a
Numerical Data Entry
object with tag address
D000
with unsigned integer format of ###.## (5,2) on
screen1
.
8 Create the following task in Poweron Task:
• Write
0
to
M000
:
To access any of the parameters
• Write
0
to
C000
:
To run/stop the drive
9 Download the application and firmware to the NQ-Series.
10 TBD: Click
Display Panel
on
File
menu.
11 Press
Set
key unless you observe P0 and rotate the POT wheel unless display changes to P0 to ....n1 and
check/set the following parameters:
• n1: Station Number Define 1
• n2: Communication Speed 192 Default (i.e. for baud rate 19200 bps)
• n3: Change it to zero
• n4: Parity check change it to 0 for even parity
12 Connect the cable to the NQ-Series and PLC. Refer to A-4-7 NQ to Mitsubishi FRS Inverter. Connect the
end RJ PORT to the FRS520E Drive.
Summary of Contents for NQ HMI
Page 1: ...NQ Series HMI GETTING STARTED GUIDE Cat No V07 EN 01 NQ3 TQ0 B NQ3 MQ0 B NQ5 SQ0 B NQ5 MQ0 B...
Page 2: ......
Page 6: ......
Page 14: ...Conformance to EC Directives Section 1 7 xiii...
Page 20: ...Specifications per model Section 2 4 6...
Page 78: ...Debugging Section 6 2 64...
Page 88: ...NQ Series diagnostics Section 7 4 74...
Page 144: ...130...