115
To define the Settings in PLC through PL7Pro Software please follow the following steps.
Using PL7Pro as a client
TSX is a server client protocol. So PLC software PL7Procan also be one client.
To work the software as a client ,some setting has to do. The settings are as follows :
1 click on the PLC menu. Click on "Define PLC Address"
2 Click on options
3 Keep wait time as 1000 or 2000
4 Click on Configuration of the drivers
5 This will pop up a window
6 Click on Unitelway driver.
7 Click on configuration
8 This will pop up an another window :
Here you have to add the number of nodes in Station List that are actually going to be present on your
network. If not defined the software will send the EOT to all the tokens except his token. If you had not
defined the node then software will send EOT (0x04) to your token also and as you are also sending the
command when received your token, then bus contamination will occur. To avoid this define the nodes in
station list, so the software will not send the EOT to your client number.