Cat. No. N142-E1-02

Single-phase Current Relay

 K8AB-AS

7

Operation and Setting Methods

Setting Ranges and Wiring Connections

Note: 1.

The DC input terminals have no polarity.

2.

The K8AB-AS3 is designed to be used in combination with 
the OMRON K8AC-CT200L Current Transformer (CT). 
(Direct input is not possible.)

Connections

1.

Input

Connect the input between the I1-COM, I2-COM, or I3-COM terminals, according to the input 
current. Malfunctions may occur if the input is connected to unused terminals and the Unit will 
not operate correctly.
Terminal I1 is not used by the K8AB-AS3.
If using the OMRON K8AC-CT200L CT, connect to terminals k and l on the K8AC-CT200L. 
(Terminals kt and lt are not used.)

2.

Power Supply
Connect the power supply to terminals A1 and A2.

Note:

Models with DC power supply have a non-isolated power supply. The input and power 
supply terminals are connected internally so the K8AB-AS will not operate normally if an 
unwanted current path is created. If an unwanted current path exists, use a model with an 
AC power supply or isolate with an external power supply.

3.

Outputs

SPDT relays are output to terminals 11, 12, and 14.

Note:

Use the recommended ferrules if using twisted wires.

DIP Switch Settings

The resetting method, relay drive method, and operating mode are set using the DIP switch located on the bottom of the Unit.

K8AB-AS

@

 does not use SW1.

Setting Method

1.

Setting Current

The current knob (SV) is used to set the current.
The current can be set to 10% to 100% of the maximum measuring current.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the 
same level.)
Use this as a guide to set the current.
The maximum measuring current will differ depending on the model and the input terminal.
Example: K8AB-AS3 Using Input Terminals I3-COM

The maximum measuring current will be 200 A AC and the setting range will be 20 to 200 A.

Model

Measuring current

Wiring 

connection

K8AB-AS1

2 to 20 mA AC/DC

I1-COM

10 to 100 mA AC/DC

I2-COM

50 to 500 mA AC/DC

I3-COM

K8AB-AS2

0.1 to 1 A AC/DC

I1-COM

0.5 to 5 A AC/DC

I2-COM

0.8 to 8 A AC/DC

I3-COM

K8AB-AS3

10 to 100 A AC (See note 2.) 

I2-COM

20 to 200 A AC (See note 2.) 

I3-COM

<For K8AB-AS3>

k

l

Load

Current input

Signal output

K8AC-
CT200L

14

12

A1

A2

I1

I2

I3

11

Relay 
signal 
output

COM

K8AB-AS3

Single-phase power

Power supply

voltage

ON

OFF

SW1
SW2
SW3
SW4

DIP switch

DIP Switch Functions

Note:

All pins are set to OFF at the factory.

SWITCH

ON 

 

OFF 

 

Resetting method

Automatic reset

---

---

NO USE

Manual reset

---

---

Relay drive method Normally closed

---

---

Normally open

---

---

Operating mode

Undercurrent

---

---

Overcurrent

---

---

ON

OFF

4

3

2

1

Summary of Contents for K8AB-AS

Page 1: ...Commercial CT input signal 0 to 1 A 0 to 5 A supported Output status can be monitored using LED indicator Model Number Structure Model Number Legend 1 Basic Model K8AB Measuring and Monitoring Relays...

Page 2: ...1 to 1 A AC DC 0 5 to 5 A AC DC 0 8 to 8 A AC DC 24 VDC not insulated K8AB AS2 24 VDC See note 1 24 VAC insulated K8AB AS2 24 VAC 100 115 VAC insulated K8AB AS2 100 115 VAC 200 230 VAC insulated K8AB...

Page 3: ...ely 30 or more of the set value Note Enabled only for overcurrent operation Indicators Power PWR Green Relay output RY Yellow Alarm outputs ALM Red Input impedance Refer to the Input Range on the prev...

Page 4: ...luence Operating value Based on ambient humidity of 65 25 to 80 5 max Operating time Based on ambient room humidity 25 to 80 10 max Influence of power supply voltage Operating value 5 max Operating ti...

Page 5: ...current path if the inputs and power supply are connected to the same line T LOCK Hysteresis 5 to 50 of operating value Lit Flashing T Operating time 0 1 to 30 s Lock Startup lock time 0 to 30 s Oper...

Page 6: ...K Alarm indicator Terminal block See notes 1 and 2 Terminal block See notes 1 and 2 Item Meaning Power indicator PWR Green Lit when power is being supplied Relay status indicator RY Yellow Lit when re...

Page 7: ...method relay drive method and operating mode are set using the DIP switch located on the bottom of the Unit K8AB AS does not use SW1 Setting Method 1 Setting Current The current knob SV is used to se...

Page 8: ...for the set period and then stay lit 4 Startup Lock Time The startup lock time is set using the startup lock time knob LOCK The startup lock time can be set to between 0 and 30 s Turn the knob while t...

Page 9: ...s 2 Make sure to use setting values appropriate for the controlled object Failure to do so can cause unintended operation and may result in accident or corruption of the product 3 Do not use thinner o...

Page 10: ...ply are connected internally so the K8AB AS will not operate normally if an unwanted current path exists If an unwanted current path exists use a K8AB model with an AC power supply or use an isolated...

Page 11: ...rating value 25 operating time 0 1 s startup lock timer 0 1 to 30 s set according to the duration of the startup current The K8AB AS3 can be set to between 10 to 100 of the rated current 10 A to 100 A...

Page 12: ...ice of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS W...

Reviews: