10

Single-phase Current Relay

 

K8AB-AS

Cat. No. N142-E1-02

Checking Operation

Overcurrents

Gradually increase the input from 80% of the setting.
The input will equal the operating value when the input 
exceeds the setting and the alarm indicator starts flashing. 
Operation can be checked by the relay outputs that will 
start after the operating time has passed.

Undercurrent

Gradually decrease the input from 120% of the setting and 
check the operation using the same method as for 
overcurrent.

Example: Overcurrent Operating Mode, Normally Open Relay Drive, 

and an Operating Time of 5 s

Connection Diagram

How to Measure the Operating Time

Overcurrent

Change the input suddenly from 0% to 120% of the set 
value and measure the time until the Unit operates.

Undercurrent

Change the input suddenly from 120% to 0% of the set 
value and measure the time until the Unit operates.

Monitoring Switch-mode Power Supplies

Switch-mode Power Supplies cannot be monitored. In 
circuits with a capacitor input, including switch-mode power 
supplies, the input capacitor recharge current flows in pulse 
form as the load current. The K8AB-AS

@

 has a built-in filter 

as a countermeasure against high frequencies and cannot 
be used to remove pulse current.

Grounding the Power Supply for K8AB Models with a DC 
Power Supply

The input and power supply must be isolated.
Models with a DC power supply have a non-isolated power 
supply. The input and power supply are connected internally 
so the K8AB-AS

@

 will not operate normally if an unwanted 

current path exists. If an unwanted current path exists, use a 
K8AB model with an AC power supply or use an isolated DC 
power supply.

Using Multiple K8AB Relays with a DC Power Supply

The input and power supply must be isolated. 
The input and power supply are connected internally so an 
unwanted current path will be created if more than one K8AB 
is used with one DC power supply, as shown in the diagram, 
and the K8AB will not operate correctly. If an unwanted 
current path exists, use a K8AB model with an AC power 
supply or use a different isolated DC power supply for each 
K8AB.

Operating Adjustment Knobs

Use a screwdriver to turn the knobs. There is a stopper to 
prevent the knob from turning any further once it has been 
turned completely to the left or right. Do not force the knob 
past these limits.

Can the K8AB be used to monitor a motor with a rated 
current of 5 A? 
If it's possible to do so, are there any precautions 
required?

The K8AB-AS1 and K8AB-AS2 cannot be used with a motor 
load. 
Use the K8AB-AS3 together with a K8AC-CT200L Current 
Transformer.
A current that is many times the rated current can flow to a 
motor due to startup current or stall current. 
The startup current of a motor is shown in the following 
graph.

Questions and Answers

Q

Set value

Current input

Alarm indicator

Relay output

Flashing

Lit

5 s

100 VAC

100 VAC

30 

0 to 10 A

A

A1

A2

±

C 100 V

Variable autotransformer

Input terminals

Power

supply

Output

Cycle counter

400 W (two in parallel)

Q

Q

Q

Q

Input signal

Input ground

K8AB

K8AB

24 VDC 
power supply

Q

Q

Summary of Contents for K8AB-AS

Page 1: ...Commercial CT input signal 0 to 1 A 0 to 5 A supported Output status can be monitored using LED indicator Model Number Structure Model Number Legend 1 Basic Model K8AB Measuring and Monitoring Relays...

Page 2: ...1 to 1 A AC DC 0 5 to 5 A AC DC 0 8 to 8 A AC DC 24 VDC not insulated K8AB AS2 24 VDC See note 1 24 VAC insulated K8AB AS2 24 VAC 100 115 VAC insulated K8AB AS2 100 115 VAC 200 230 VAC insulated K8AB...

Page 3: ...ely 30 or more of the set value Note Enabled only for overcurrent operation Indicators Power PWR Green Relay output RY Yellow Alarm outputs ALM Red Input impedance Refer to the Input Range on the prev...

Page 4: ...luence Operating value Based on ambient humidity of 65 25 to 80 5 max Operating time Based on ambient room humidity 25 to 80 10 max Influence of power supply voltage Operating value 5 max Operating ti...

Page 5: ...current path if the inputs and power supply are connected to the same line T LOCK Hysteresis 5 to 50 of operating value Lit Flashing T Operating time 0 1 to 30 s Lock Startup lock time 0 to 30 s Oper...

Page 6: ...K Alarm indicator Terminal block See notes 1 and 2 Terminal block See notes 1 and 2 Item Meaning Power indicator PWR Green Lit when power is being supplied Relay status indicator RY Yellow Lit when re...

Page 7: ...method relay drive method and operating mode are set using the DIP switch located on the bottom of the Unit K8AB AS does not use SW1 Setting Method 1 Setting Current The current knob SV is used to se...

Page 8: ...for the set period and then stay lit 4 Startup Lock Time The startup lock time is set using the startup lock time knob LOCK The startup lock time can be set to between 0 and 30 s Turn the knob while t...

Page 9: ...s 2 Make sure to use setting values appropriate for the controlled object Failure to do so can cause unintended operation and may result in accident or corruption of the product 3 Do not use thinner o...

Page 10: ...ply are connected internally so the K8AB AS will not operate normally if an unwanted current path exists If an unwanted current path exists use a K8AB model with an AC power supply or use an isolated...

Page 11: ...rating value 25 operating time 0 1 s startup lock timer 0 1 to 30 s set according to the duration of the startup current The K8AB AS3 can be set to between 10 to 100 of the rated current 10 A to 100 A...

Page 12: ...ice of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS W...

Reviews: