background image

Cat. No. N142-E1-02

Single-phase Current Relay

 K8AB-AS

9

Safety Precautions

Precautions for Safe Use

Make sure to follow the instructions below to ensure safety.

1.

Do not use or keep this product in the following environments.

Outdoors, or places subject to direct sunlight or wearing 
weather.

Places where dust, iron powder, or corrosive gases (in 
particular, sulfuric or ammonia gas) exist.

Places subject to static electricity or inductive noise.

Places where water or oil come in contact with the product.

2.

Make sure to install this product in the correct direction.

3.

There is a remote risk of electric shock. Do not touch terminals 
while electricity is being supplied.

4.

Make sure to thoroughly understand all instructions in the 
Instructions Manual before handling this product.

5.

Make sure to confirm terminal makings and polarity for correct 
wiring.

6.

Tighten terminal screws firmly using the following torque.
Recommended tightening torque: 0.49 N·m
Maximum tightening torque: 

0.54 N·m max.

7.

Operating ambient temperature and humidity for this product 
must be within the indicated rating when using this product.

8.

There is a remote risk of explosion. Do not use this product where 
flammable or explosive gas exists.

9.

Make sure that no weight rests on the product after installation.

10.

To enable an operator to turn off this product easily, install 
switches or circuit breakers that conform to relevant requirements 
of IEC60947-1 and IEC60947-3, and label them appropriately.

11.

For DC input, use a SELV power-supply capable of overcurrent 
protection. Specifically, a SELV power-supply has a double or 
reinforced insulation for input and output, and output voltage of 
30 Vr.m.s with 42.4 V at peak or DC60V maximum.
Recommended power-supply: Model S8VS-06024

@

. (Omron 

product)

Precautions for Correct Use

For Proper Use

1.

Do not use the product in the following locations.

Places subject to radiant heat from heat generating devices.

Places subject to vibrations or physical shocks.

2.

Make sure to use setting values appropriate for the controlled 
object. Failure to do so can cause unintended operation, and may 
result in accident or corruption of the product.

3.

Do not use thinner or similar solvent for cleaning. Use commercial 
alcohol.

4.

When discarding, properly dispose of the product as industrial 
waste.

5.

Only use this product within a board whose structure allows no 
possibility for fire to escape.

About Installation

1.

When wiring, use only recommended crimp terminals.

2.

Do not block areas around the product for proper dissipation of 
heat. (If you do not secure space for heat dissipation, life cycle of 
the product will be compromised.)

3.

To avoid electrical shocks, make sure that power is not supplied to 
the product while wiring.

4.

To avoid electrical shocks, make sure that power is not supplied to 
the product when performing DIP switch settings.

Noise Countermeasures

1.

Do not install the product near devices generating strong high 
frequency waves or surges.

2.

When using a noise filter, check the voltage and current and 
install it as close to the product as possible.

3.

In order to prevent inductive noise, wire the lines connected to the 
product separately from power lines carrying high voltages or 
currents. Do not wire in parallel with or on the same cable as 
power lines. 
Other measures for reducing noise include running lines along 
separate ducts and using shield lines.

To avoid faulty operations, 
malfunctions, or failure, observe the 
following operating instructions.

1.

When turning on the power, make sure to realize rated voltage 
within 1 second from the time of first supply of electricity.

2.

Make sure to use power supply for operations, inputs, and 
transformer with the appropriate capacity and rated burden.

3.

Maintenance and handling of this product may only be performed 
by qualified personnel.

4.

Distortion ratio of input wave forms must be 30% or less. Use of 
this product with circuits that have large distortion in wave forms 
may result in unwanted operations.

5.

Using this product for thyristor controls or inverters will result in 
errors.

6.

When setting the volume, adjust the control from the minimum 
side to the maximum side.

Summary of Contents for K8AB-AS

Page 1: ...Commercial CT input signal 0 to 1 A 0 to 5 A supported Output status can be monitored using LED indicator Model Number Structure Model Number Legend 1 Basic Model K8AB Measuring and Monitoring Relays...

Page 2: ...1 to 1 A AC DC 0 5 to 5 A AC DC 0 8 to 8 A AC DC 24 VDC not insulated K8AB AS2 24 VDC See note 1 24 VAC insulated K8AB AS2 24 VAC 100 115 VAC insulated K8AB AS2 100 115 VAC 200 230 VAC insulated K8AB...

Page 3: ...ely 30 or more of the set value Note Enabled only for overcurrent operation Indicators Power PWR Green Relay output RY Yellow Alarm outputs ALM Red Input impedance Refer to the Input Range on the prev...

Page 4: ...luence Operating value Based on ambient humidity of 65 25 to 80 5 max Operating time Based on ambient room humidity 25 to 80 10 max Influence of power supply voltage Operating value 5 max Operating ti...

Page 5: ...current path if the inputs and power supply are connected to the same line T LOCK Hysteresis 5 to 50 of operating value Lit Flashing T Operating time 0 1 to 30 s Lock Startup lock time 0 to 30 s Oper...

Page 6: ...K Alarm indicator Terminal block See notes 1 and 2 Terminal block See notes 1 and 2 Item Meaning Power indicator PWR Green Lit when power is being supplied Relay status indicator RY Yellow Lit when re...

Page 7: ...method relay drive method and operating mode are set using the DIP switch located on the bottom of the Unit K8AB AS does not use SW1 Setting Method 1 Setting Current The current knob SV is used to se...

Page 8: ...for the set period and then stay lit 4 Startup Lock Time The startup lock time is set using the startup lock time knob LOCK The startup lock time can be set to between 0 and 30 s Turn the knob while t...

Page 9: ...s 2 Make sure to use setting values appropriate for the controlled object Failure to do so can cause unintended operation and may result in accident or corruption of the product 3 Do not use thinner o...

Page 10: ...ply are connected internally so the K8AB AS will not operate normally if an unwanted current path exists If an unwanted current path exists use a K8AB model with an AC power supply or use an isolated...

Page 11: ...rating value 25 operating time 0 1 s startup lock timer 0 1 to 30 s set according to the duration of the startup current The K8AB AS3 can be set to between 10 to 100 of the rated current 10 A to 100 A...

Page 12: ...ice of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS W...