250
Error Processing
Section 9-2
Other Errors
Coordinator
Module Fatal
error
0006
A402.14: Coor-
dinator Module
Fatal Error Flag
A fatal error occurred in the Coordi-
nator Module.
Remove the cause of the error in the
Coordinator Module and then clear
the error.
Coordinator
Module WDT
error
0001
A402.13: Coor-
dinator Module
WDT Error Flag
A watchdog timer error occurred in
the Coordinator Module.
Turn the power OFF and ON again.
LED indicator status
Error
Error
code
(A400)
Flag and
word data
Probable cause
Possible remedy
Communica-
tions error
None
None
A communications
error occurred
between the peripheral
port and the con-
nected device.
Check the cables.
Also, check the setting
of DIP Switch pin 2
and the communica-
tions settings for the
peripheral port in the
System Setup and cor-
rect any mistakes.
Communica-
tions error
None
None
A communications
error occurred
between the RS-232C
port and the con-
nected device.
Check the host link
port settings in the
System Setup.
Check the cable wir-
ing.
If a host computer is
connected, check the
host computer’s serial
port settings and the
program.
Communica-
tions error
None
None
A communications
error occurred
between the RS-422A
port and the con-
nected device.
Check whether the
servo driver settings in
the System Setup are
correct.
Check the cable wir-
ing.
Check the operating
status of the con-
nected servo driver.
Error
Error
code (in
A400)
Flag and word
data
Probable cause
Possible remedy
Power Supply
Unit
POWER
Lit
Coordinator
Module
RDY
Lit
RUN
Lit
ERR
---
PRPHL
OFF
COMM1
---
COMM2
---
Power Supply
Unit
POWER
Lit
Coordinator
Module
RDY
Lit
RUN
Lit
ERR
---
PRPHL
---
COMM1
OFF
COMM2
OFF
Power Supply
Unit
POWER
Lit
Coordinator
Module
RDY
Lit
RUN
Lit
ERR
---
PRPHL
---
COMM1
---
COMM2
OFF
Summary of Contents for HOME SECURITY SYSTEM - MOTION SENSOR FQM1-CM001
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 11: ...xii...
Page 23: ...xxiv Data Backup 5...
Page 53: ...30 Function Tables Arranged by Purpose Section 1 7...
Page 71: ...48 Memory Block Diagram Section 2 7...
Page 254: ...231 Analog Outputs Section 7 10...
Page 255: ...232 Analog Outputs Section 7 10...
Page 263: ...240 Connecting the CX Programmer Section 8 2...
Page 285: ...262 Inspections Section 10 1...
Page 397: ...374 Auxiliary Area Allocations Appendix D...
Page 409: ...386 Index...
Page 411: ...388...