188
Pulse Outputs
Section 7-6
• Select pulse output 1 or 2.
2.
Wire the output.
• Output: CW and CCW
• Output power supply: 5 V DC
3.
Make the necessary System Setup settings (Pulse Output Tab Page
−
Op-
eration Mode).
• Set the pulse output operation mode (in the Pulse Output Tab Page
−
Operation Mode) to relative pulse output or absolute linear pulse output.
• Set the clock speed for pulse outputs 1 and 2.
4.
Create the necessary ladder programming.
• Use PLS2(887) to start pulse output control with trapezoidal acceleration/
deceleration from the specified port (acceleration and deceleration are
specified separately).
• Use INI(880) to stop pulse output from the specified port.
• Use PRV(881) to read the pulse output PV of the specified port.
One-shot Pulse Output (STIM(980))
1,2,3...
1.
Determine pulse output port.
• Select pulse output 1 or 2.
2.
Wire the output.
3.
Make the necessary System Setup settings.
• Set the pulse output operation mode (in the Pulse Output Tab Page
−
Operation Mode) to
1 shot
.
4.
Create the necessary ladder programming.
• Use STIM(980) (with C1 = #0001 or #0002) to turn ON the one-shot pulse
output.
Note
The STIM(980) one-shot pulse output function can be used at the same time
as an STIM(980) timer interrupt function (one-shot timer or scheduled timer).
Pulse Counter Timer Function (STIM(980))
1,2,3...
1.
Determine pulse output port.
• Select pulse output 1 or 2.
2.
Make the necessary System Setup settings.
INI
PLS2
PRV
A621
A620
A623
A622
A624
A625
CW
CCW
CW
CCW
Pulse output
port 1
Pulse output
port 2
Single-phase pulse output
with trapezoidal
acceleration/deceleration
Start
output
Ladder program
Ladder program
Stop pulse output.
Set number of output pulses.
Target frequency: 20 Hz to 1 MHz
Acceleration/deceleration rates
(set separately)(1 or 2 ms cycle,
1 Hz to 9,999 Hz)
Start pulse output.
Pulse output
mode
System Setup
Mode settings for
ports 1 and 2
Port 1
Port 2
Port 1
Port 2
Refresh status (once each cycle
just after instruction execution)
Pulse output status
Pulse output PV
Refresh PV (once each cycle)
Refresh PV (immediate refresh)
Read pulse output PV
Starting frequency: 0 Hz to 1 MHz
HIGH-SPEED
COUNTER
PV READ
MODE CONTROL
PULSE
OUTPUT
Summary of Contents for HOME SECURITY SYSTEM - MOTION SENSOR FQM1-CM001
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 11: ...xii...
Page 23: ...xxiv Data Backup 5...
Page 53: ...30 Function Tables Arranged by Purpose Section 1 7...
Page 71: ...48 Memory Block Diagram Section 2 7...
Page 254: ...231 Analog Outputs Section 7 10...
Page 255: ...232 Analog Outputs Section 7 10...
Page 263: ...240 Connecting the CX Programmer Section 8 2...
Page 285: ...262 Inspections Section 10 1...
Page 397: ...374 Auxiliary Area Allocations Appendix D...
Page 409: ...386 Index...
Page 411: ...388...