Wiring Precautions
Section 3-6
Inductive Loads
When an inductive load is connected to I/O, connect a surge suppressor or
diode in parallel with the load as shown below.
Note
Use surge suppressors and diodes with the following specifications.
External Wiring
Observe the following precautions for I/O wiring, power supply wiring, and
power line wiring.
• When multi-conductor signal cable is being used, do not combine I/O
wires and other control wires in the same cable.
• If wiring racks are parallel, allow at least 300 mm between the racks.
• If the I/O wiring and power cables must be placed in the same duct, they
must be shielded from each other using grounded steel sheet metal.
L
IN
COM
OUT
COM
OUT
COM
L
+
Diode
DC input
Relay output or
triac output
Surge suppressor
Relay output or
transistor output
Diode
Surge suppressor specifications
Diode specifications
Resistor: 50
Ω
Capacitor: 0.47
µ
F
Voltage: 200 V
Breakdown voltage: 3 times load voltage min.
Mean rectification current: 1 A
FQM1 I/O wiring
FQM1 power supply and
general control circuit wiring
Power lines
Ground to 100
Ω
or less
Low-current cables
Control cables
Control cables
300 mm min.
300 mm min.
FQM1 I/O wiring
FQM1 power
supply and general
control wiring
Power lines
Steel sheet metal
Ground to 100
Ω
or less
200 mm min.
Summary of Contents for HOME SECURITY SYSTEM - MOTION SENSOR FQM1-CM001
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 11: ...xii...
Page 23: ...xxiv Data Backup 5...
Page 53: ...30 Function Tables Arranged by Purpose Section 1 7...
Page 71: ...48 Memory Block Diagram Section 2 7...
Page 254: ...231 Analog Outputs Section 7 10...
Page 255: ...232 Analog Outputs Section 7 10...
Page 263: ...240 Connecting the CX Programmer Section 8 2...
Page 285: ...262 Inspections Section 10 1...
Page 397: ...374 Auxiliary Area Allocations Appendix D...
Page 409: ...386 Index...
Page 411: ...388...