110
Synchronous Data Refresh
Section 5-4
Synchronous Data
Note
(1) Synchronous data for Coordinator Modules is fixed to general-purpose
(ladder execution results) data.
(2) If there is no synchronous data to be sent, select no data for
Select Syn-
chronous Data
in the System Setup to shorten the synchronous data
transfer time.
(3) Auxiliary Area data is transferred when input and output refresh method
is set to
Immediate refresh
and the synchronous data is set to an analog
input or analog output value in the System Setup.
5-4-3
Synchronous Data Link Bit Area
+0
+1
+2
+3
Normal (via Ladder)
Counter 1 values
Counter 2 values
Pulse output 1
Pulse output 2
Analog input
Analog output 1
Analog output 2
Inner I/O input
(Built-in input)
4 words of data transferred for each Module
System Setup
Select Synchronous
Data
Set in upper
2 words
Example: 4 words of data sent
by Motion Control Module #1
Counter 1 values
Pulse output 1
Transfer
System Setup
Select Synchronous
Data
Set in lower
2 words
Above example: Motion Control
Module #1 sends its high-speed
counter 1 PV and pulse output 1 PV
as the synchronous data link bits.
Synchronous Data
Link Bit Areas in
Coordinator and
Motion Control
Modules
Word
address
(See note
1.)
Bits
Method for selecting type of synchronous data
Sent from Coordina-
tor Module
CIO 0200
00 to 15
Fixed to general-purpose data (e.g., ladder execution results)
CIO 0201
00 to 15
CIO 0202
00 to 15
Fixed to general-purpose data (e.g., ladder execution results)
CIO 0203
00 to 15
Sent from Motion
Control Module #1
CIO 0204
00 to 15
Set using upper 2 words of
Select Synchronous Data
in the System
Setup for Motion Control Module #1.
CIO 0205
00 to 15
CIO 0206
00 to 15
Set using lower 2 words of
Select Synchronous Data
in the System
Setup for Motion Control Module #1.
CIO 0207
00 to 15
Sent from Motion
Control Module #2
CIO 0208
00 to 15
Set using upper 2 words of
Select Synchronous Data
in the System
Setup for Motion Control Module #2.
CIO 0209
00 to 15
CIO 0210
00 to 15
Set using lower 2 words of
Select Synchronous Data
in the System
Setup for Motion Control Module #2.
CIO 0211
00 to 15
Sent from Motion
Control Module #3
CIO 0212
00 to 15
Set using upper 2 words of
Select Synchronous Data
in the System
Setup for Motion Control Module #3.
CIO 0213
00 to 15
CIO 0214
00 to 15
Set using lower 2 words of
Select Synchronous Data
in the System
Setup for Motion Control Module #3.
CIO 0215
00 to 15
Summary of Contents for HOME SECURITY SYSTEM - MOTION SENSOR FQM1-CM001
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 11: ...xii...
Page 23: ...xxiv Data Backup 5...
Page 53: ...30 Function Tables Arranged by Purpose Section 1 7...
Page 71: ...48 Memory Block Diagram Section 2 7...
Page 254: ...231 Analog Outputs Section 7 10...
Page 255: ...232 Analog Outputs Section 7 10...
Page 263: ...240 Connecting the CX Programmer Section 8 2...
Page 285: ...262 Inspections Section 10 1...
Page 397: ...374 Auxiliary Area Allocations Appendix D...
Page 409: ...386 Index...
Page 411: ...388...