219
Analog Input Functions
Section 7-9
Auxiliary Area
Word
Bits
Function
Settings
Controlled
by
A550
00 to 15
Analog Input PV
Contains the value input from the analog input port
(using either the END refresh or immediate refresh)
in 4-digit hexadecimal.
The PV range depends on the input range:
• 0 to 10 V:
FE70 to 20D0 hex
• 0 to 5 V or 1 to 5 V: FF38 to 1068 hex
•
−
10 to 10 V:
DDA0 to 2260 hex
Motion
Control
Module
A552
00
Analog Input
Status
Analog Input
User Adjustment
Completed
OFF: Not adjusted
ON:
Adjustment completed
01 to 06
Reserved
07
Analog Sampling
Started
OFF: Not started
ON:
Started
08
Factory Adjustment
Data Error
OFF: No Error
ON:
Error
(Checked at startup.)
09
User Adjustment
Data Error
OFF: No Error
ON:
Error
(Checked at startup.)
10 to 14
Reserved
---
15
Analog Input
Status
Analog Input
Analog Sampling
Overlap
OFF: Normal sampling
ON:
The next sampling
operation occurred
before the present
sampling operation
completed.
Motion
Control
Module
A559
01 to 15
Analog Input
Status
Analog Input
Number of Samples Indicates the number of data
samples actually input since
sampling started.
Motion
Control
Module
A560
00 to 15
Analog Out-
put 1 Output
Value
When an END refresh is selected, the 4-digit hexadecimal value set
here by the user is output from analog output port 1.
When immediate refreshing is selected, the 4-digit hexadecimal value
being output from analog output port 1 is stored here for monitoring.
The output value range depends on the output range, as shown below.
• 0 to 10 V, 0 to 5 V or 1 to 5 V: FF38 to 1068 hex
•
−
10 to 10 V: EA84 to 157C hex
Note
1. Set the analog output method (END or immediate refreshing) with the
System Setup’s output method setting. A setting of 0 hex specifies an
END refresh. This setting applies to both analog output 1 and 2.
2. Specify the output range with the output 1 setting.
With imme-
diate
refresh:
Motion
Control
Module
With END
refresh:
User
A561
00 to 15
Analog Out-
put 2 Output
Value
This word has the same settings as the analog output 1 output value
(A560), above. (When an END refresh is selected, set the value to out-
put from analog output port 2. When an immediate refresh is selected,
the output value is stored here for monitoring.)
Note
1. Set the analog output method (END or immediate refresh) with the
System Setup’s output method setting. A setting of 0 hex specifies an
END refresh. This setting applies to both analog output 1 and 2.
2. Specify the output range with the output 2 setting.
Summary of Contents for HOME SECURITY SYSTEM - MOTION SENSOR FQM1-CM001
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 11: ...xii...
Page 23: ...xxiv Data Backup 5...
Page 53: ...30 Function Tables Arranged by Purpose Section 1 7...
Page 71: ...48 Memory Block Diagram Section 2 7...
Page 254: ...231 Analog Outputs Section 7 10...
Page 255: ...232 Analog Outputs Section 7 10...
Page 263: ...240 Connecting the CX Programmer Section 8 2...
Page 285: ...262 Inspections Section 10 1...
Page 397: ...374 Auxiliary Area Allocations Appendix D...
Page 409: ...386 Index...
Page 411: ...388...