3-4 Wiring the Power Supply
3-4-1 Wiring the Power Supply to the Gateway Unit
Power (24 VDC) is supplied directly from a power source to the Gateway Unit.
Precautions for Correct Use
Do not allow the wiring between the Gateway Unit and the power supply to exceed 3 m.
z
Selecting a DC Power Supply
The DC power supply must satisfy the following conditions.
For Slave Units with network power supply, the power for external I/O is also supplied from the
power supply connected to the Gateway Unit (through the Flat Cable). When determining the output
current of the power supply, always include the actual load currents and the current consumptions of
the external I/O.
Refer to documentation for each Slave Unit for information on Slave Unit current consumptions.
Item
Specification
Output voltage
24 VDC
±
10%
Output ripple
600 mVp-p
Output current
The capacity of the power supply must be equal to the sum of the
following current consumptions or greater.
•
Current consumptions of all Word Slave Units and Repeater Units
•
Current consumptions of all Bit Slave Units plus the current
consumptions of the external I/O
Isolation
The output must be isolated from both the AC power supply and the
case ground.
L
L
RUN
ERR
RD
SD
RD
REGIST
REG
SD
NS
MS
STATION No.
X10 MODE
X1 B.RATE
DR0
DR1
DCN
REGS
DA
DB
DG
SLD
FG
DC24V INPUT
GQ-CRM21
1
2
4
.
.
RESET
Communications
Connector
Communications
power supply
(24 VDC)
Power connector
3 m max.
Summary of Contents for GQ-CRM21
Page 1: ...OPERATION MANUAL Cat No W489 E1 01 GQ CRM21 CompoNet Gateway Unit for CC Link ...
Page 21: ...1 Overview 1 1 Overview 1 1 ...
Page 25: ...2 Description of Gateway Unit 2 1 Specifications 2 1 2 2 Component Names and Functions 2 4 ...
Page 38: ...2 13 CompoNet Gateway Unit for CC Link Operation Manual 2 2 Component Names and Functions 2 ...
Page 102: ......