2 - 1
CompoNet Gateway Unit for CC-Link Operation Manual
2-
1 Specif
ica
ti
ons
2
2-1 Specifications
2-1-1 General Specifications
Item
Specification
Unit power supply voltage
21.6 to 26.4 VDC (24 VDC
±
10%) (Supplied from power supply connector.)
Current
consumption
Communications
power supply
3.80 A at 24 VDC
Internal current
power
consumption
0.13 A at 24 VDC
Noise immunity
Conforms to IEC 61000-4-4, 2.0 kV
Vibration resistance
Malfunction: 10 to 60 Hz with 0.7-mm double amplitude, 60 to 150 Hz, 50 m/s
2
for 80 min in X, Y, and Z directions
Shock resistance
150 m/s
2
, 3 times in 6 directions on 3 axes
Dielectric strength
500 VAC
Installation method
Mounted to DIN Track or by using M4 screws
Ambient operating temperature
0 to 55
°
C
Ambient operating humidity
10% to 90% (with no condensation)
Ambient storage temperature
−
25 to 65
°
C
Weight
110 g max.
Ambient operating atmosphere
No corrosive gases