3 - 15
CompoNet Gateway Unit for CC-Link Operation Manual
3-7
Communic
ations S
e
ttings
3
2. Make the following settings on the CC-Link Station Information Dialog Box.
• CompoNet communications mode 0, 1, 2, 4, or 5
(1) Set the station type to
Ver. 2 Remote device station
.
(2) Set the exclusive station count to
Exclusive station 4
.
(3) Set the expanded cyclic setting as shown below according to the communication mode that was
set on the mode DIP switch.
• CompoNet communications mode 3 or 6
(1) Set the station type to
Ver. 1 Remote device station
or
Remote device station
.
(2) Set the exclusive station count to
Exclusive station 4
.
Communication mode
CC-Link expanded cyclic setting
Communications mode 0
Octuple
Communications mode 1
Quadruple
Communications mode 2
Double
Communications mode 4
Quadruple
Communications mode 5
Double
(1)
(2)
(3)