4 - 13
CompoNet Gateway Unit for CC-Link Operation Manual
4-2 Memory
Map
4
CC-Link Status
• Remote Inputs (RX)
• Remote Outputs (RY)
*1
“n” depends on the communications mode as shown below when the first refresh device address in the remote
input (RX) area or remote output (RY) area is 0 and the station number of the Gateway Unit is 1.
Communications mode 0 or 4: 10, Communications mode 1 or 5: C, Communications mode 2: 6, or Communi-
cations mode 3: 2.
*2
These flags are disabled because the Gateway Unit does not require initialization.
*3
The Error Status Flag will not automatically turn OFF even if the cause of the error is removed.
Remove the cause of the error, and then turn ON the Error Reset Request Flag.
*4
This flag turns ON when the power supply is turned ON or after resetting with the reset switch.
Bit address*1
Name
RXn0
Initial Data Processing Request Flag*2
RXn1
Initial Data Setting Completed Flag*2
RXn2
Error Status Flag*3
RXn3
Remote Station Ready Flag*4
RXn4
Reserved.
RXn5
RXn6
RXn7
Defined by OS.
Bit address*1
Name
RYn0
Initial Data Processing Completed Flag*2
RYn1
Initial Data Setting Request Flag*2
RYn2
Error Reset Request Flag*3
RYn3
Reserved.
RYn4
RYn5
RYn6
Defined by OS.
RYn7
Remote Station
Ready Flag
Error Reset
Request Flag
Error Status Flag
Error occurred.
ON
ON
ON
OFF
OFF
OFF
Summary of Contents for GQ-CRM21
Page 1: ...OPERATION MANUAL Cat No W489 E1 01 GQ CRM21 CompoNet Gateway Unit for CC Link ...
Page 21: ...1 Overview 1 1 Overview 1 1 ...
Page 25: ...2 Description of Gateway Unit 2 1 Specifications 2 1 2 2 Component Names and Functions 2 4 ...
Page 38: ...2 13 CompoNet Gateway Unit for CC Link Operation Manual 2 2 Component Names and Functions 2 ...
Page 102: ......