2 - 10
Description of Gateway Unit
CompoNet Gateway Unit for CC-Link Operation Manual
2-
2-
2 Swit
ch Set
tin
gs
2
Supplemental Information
To press the CompoNet setting buttons, open the cover as shown below.
CC-Link Communications Section
z
Station Number Switch
The station number switch sets the station number of the Gateway Unit on the CC-Link network.
z
Baud Rate DIP Switch
The baud rate DIP switch sets the baud rate of the Gateway Unit on the CC-Link network.
Set the baud rate of the Gateway Unit to the same value as the CC-Link Master Unit.
• Baud Rate Setting
*1
Always leave pin 4 turned OFF. It is reserved.
Number
Description
Remarks
1 to 61
Set the station number of the Gateway Unit on the
CC-Link network.
Default: 00
0 or 62 to 99
Do not set.
The L ERR indicator will light.
Pin 1
Pin 2
Pin 3
Pin 4*1
Baud rate
OFF
OFF
OFF
OFF
156 kbps (default)
OFF
OFF
ON
OFF
625 kbps
OFF
ON
OFF
OFF
2.5 Mbps
OFF
ON
ON
OFF
5 Mbps
ON
OFF
OFF
OFF
10 Mbps
Open from here.
X 1 0
X 1
1
2
3
4
O