75
Functions Common to All Slave Units
Section 6-1
Checking Using the
Status Areas
Refer to bits 0 and 1 in
6-1-4
Input Filter (Input Units Only)
Description
An input value is read more than once during a set time interval. The input
value can be set to be enabled only when all the read values are the same.
This function operates for all input points in one Slave Unit.
The following settings are possible:
No delay (no filter), or 4, 8, 16, 32, 64, 128, or 256 ms.
OFF-ON Delay
When the input data turns ON, the input data is read 4 times at a set time (1/4
of the time setting). The internal input data turns ON only when all four values
are ON. The ON timing is delayed by the value of the input time constant.
ON-OFF Delay
When the input data turns OFF, the input data is read 5 times at a set interval
(1/5 of the OFF response time setting). The internal input data turns OFF only
when all values are OFF. The OFF timing is delayed by the value of the OFF
response time.
This function can also be used to implement an OFF delay.
To enable reading pulses shorter than the communications cycle time, set the
OFF response time to a value longer than the communications cycle time.
(The input may remain ON if the input pulse interval is too short.)
Settings Using the Network Configurator
1,2,3...
1.
Turn ON the power supply to the EtherNet/IP Slave Unit.
2.
Double-click the icon of the Slave Unit to set in the Network Configuration
Window to open the Edit Device Parameters Window. (Alternatively, right-
click the icon and select
Parameters - Edit
from the pop-up menu.)
3.
Select an input in the
Input Point Group Setting
Group and set the Off-On
Delay or On-Off delay from the pull-down menu.
OFF
ON
ON
OFF
ON
ON
OFF
OFF
4
3
2
1
Input data
The internal input data
remains OFF because the
read input data was not ON
all 4 times.
ON
ON
ON
ON
4
3
2
1
OFF
ON
ON
OFF
Input data
ON delay (= input filter time)
The internal input
data turns ON
because the read
input data was
ON all 4 times.
OFF
1
ON
5
OFF
OFF
ON
4
3
2
OFF
ON
ON
OFF
Input data
The internal input
data remains ON
because read input
data was not OFF
all 5 times.
OFF
OFF
OFF
OFF
4
3
2
1
OFF
5
OFF
ON
ON
OFF
Input data
The internal
input data turns
OFF because
the read input
data was OFF
all 5 times.
OFF-delay time
Summary of Contents for ERT1 Series
Page 1: ...OPERATION MANUAL Cat No W481 E1 02 EtherNet IP Slave Units ERT1 Series...
Page 2: ......
Page 3: ...ERT1 Series EtherNet IP Slave Units Operation Manual Revised November 2010...
Page 4: ...iv...
Page 6: ...vi...
Page 8: ...viii...
Page 14: ...xiv...
Page 58: ...38 Recommended Network Devices Section 2 2...
Page 62: ...42 Basic Specifications of Slave Units Section 3 1...
Page 78: ...58 Screw less Clamp Terminals Section 4 2...
Page 92: ...72 Environment resistive Slave Units Section 5 2...
Page 102: ...82 Maintenance and Replacement Section 7 3...
Page 106: ...86 Revision History...
Page 107: ......