![Omron ERT1 Series Operation Manual Download Page 75](http://html1.mh-extra.com/html/omron/ert1-series/ert1-series_operation-manual_743568075.webp)
55
Screw-less Clamp Terminals
Section 4-2
(2) Ethernet Connector
The network communications cable is connected to this connector.
(3) Power Supply Connector
The communications and Unit power supply is connected to this connector.
Applicable Ferrules
(4) Communications Indicators: MS and NS
These indicators show the Unit communications status and network commu-
nications status.
(5) and (6) Terminal Blocks 1 and 2
The I/O devices and output power supply are connected to these terminal
blocks.
(7) and (8) I/O Indicators
These indicators show the ON/OFF status of the I/O and the error status of
connected devices.
Indicators
Communications
Indicators
Refer to
3-1-3 Communications Indicators
.
I/O Indicators
The meanings of the input indicators are given in the following table.
Setting the Node
Address
The rotary switches are used to set the lower digits of the IP address.
Manufacturer
Model
Applicable wire size
Phoenix Contact
AI-0.5-10
0.5 mm
2
(AWG 20)
Nihon Weidmuller
H 0.5/16 D
0.5 mm
2
(AWG 20)
24 V DC
0 V DC
Terminal
Specification
+
24 V DC
−
0 V DC
Indicator name
Status
Color
Meaning (main error)
0 to 15
Yellow
Lit yellow when input or output is
ON.
Red
Flashing red when the load is dis-
connected.
Automatically reset when the load
is connected.
Red
Lit red when the load is short-cir-
cuited.
Automatically reset when the
short-circuit is removed.
OFF
Not lit when input or output is OFF.
I/O
Green
Lit green when I/O power is being
supplied.
OFF
Not lit when I/O power is not being
supplied.
Setting method
Two hexadecimal digits
Setting range
01 to FE
Summary of Contents for ERT1 Series
Page 1: ...OPERATION MANUAL Cat No W481 E1 02 EtherNet IP Slave Units ERT1 Series...
Page 2: ......
Page 3: ...ERT1 Series EtherNet IP Slave Units Operation Manual Revised November 2010...
Page 4: ...iv...
Page 6: ...vi...
Page 8: ...viii...
Page 14: ...xiv...
Page 58: ...38 Recommended Network Devices Section 2 2...
Page 62: ...42 Basic Specifications of Slave Units Section 3 1...
Page 78: ...58 Screw less Clamp Terminals Section 4 2...
Page 92: ...72 Environment resistive Slave Units Section 5 2...
Page 102: ...82 Maintenance and Replacement Section 7 3...
Page 106: ...86 Revision History...
Page 107: ......