![Omron ERT1 Series Operation Manual Download Page 100](http://html1.mh-extra.com/html/omron/ert1-series/ert1-series_operation-manual_743568100.webp)
80
Maintenance and Replacement
Section 7-3
7-3
Maintenance and Replacement
This section describes the routine cleaning and inspection recommended as
regular maintenance, as well as the Unit replacement procedure required if an
EtherNet/IP Unit needs to be replaced.
7-3-1
Cleaning
Clean the EtherNet/IP Unit regularly as described below in order to keep the
network in its optimal operating condition.
• Wipe the Unit daily with a dry, soft cloth.
• When a spot can’t be removed with a dry cloth, dampen the cloth with a
neutral cleanser (2% solution), wring out the cloth, and wipe the Unit.
• A smudge may remain on the Unit from gum, vinyl, or tape that was left on
for a long time. Remove the smudge when cleaning.
!Caution
Never use volatile solvents such as paint thinner, benzene, or chemical wipes.
These substances could damage the surface of the Unit.
7-3-2
Inspection
Be sure to inspect the system periodically to keep it in its optimal operating
condition. In general, inspect the system once every 6 to 12 months, but
inspect more frequently if the system is used with high temperature or humid-
ity or under dirty/dusty conditions.
Inspection Equipment
Prepare the following equipment before inspecting the system.
Normally Required
Equipment
Have a standard and Phillips-head screwdriver, multimeter, alcohol, and a
clean cloth.
Occasionally Required
Equipment
Depending on the system conditions, a synchroscope, oscilloscope, ther-
mometer, or hygrometer (to measure humidity) might be needed.
Inspection Procedure
Check the items in the following table and correct any items that are below
standard.
7-3-3
Unit Replacement Procedure
The network consists of the EtherNet/IP Unit and EtherNet/IP Slave Units.
The entire network is affected when a Unit is faulty. A faulty Unit must be
repaired or replaced quickly.
Precautions
Observe the following precautions when replacing a faulty Unit.
Item
Standard
Inspection
Environmental
conditions
Ambient and cabinet temperature
Refer to specifications for
each Slave Unit.
Thermometer
Ambient and cabinet humidity
Refer to specifications for
each Slave Unit.
Hygrometer
Dust/dirt accumulation
None
Visual
Installation
Are the Units secure?
No looseness
Phillips screw-
driver
Are the Ethernet cable connectors
fully inserted?
No looseness
Phillips screw-
driver
Are the external wiring screws
tight?
No looseness
Phillips screw-
driver
Are the cables in good condition?
No external abnormalities
Visual
Summary of Contents for ERT1 Series
Page 1: ...OPERATION MANUAL Cat No W481 E1 02 EtherNet IP Slave Units ERT1 Series...
Page 2: ......
Page 3: ...ERT1 Series EtherNet IP Slave Units Operation Manual Revised November 2010...
Page 4: ...iv...
Page 6: ...vi...
Page 8: ...viii...
Page 14: ...xiv...
Page 58: ...38 Recommended Network Devices Section 2 2...
Page 62: ...42 Basic Specifications of Slave Units Section 3 1...
Page 78: ...58 Screw less Clamp Terminals Section 4 2...
Page 92: ...72 Environment resistive Slave Units Section 5 2...
Page 102: ...82 Maintenance and Replacement Section 7 3...
Page 106: ...86 Revision History...
Page 107: ......