Overview of System Startup Procedure
Section 2-1
The IP address will be as follows when the rotary switches are set to 01 to
FE hex: 192.168.250.n (n = Decimal equivalent of value set on rotary
switches).
2-1-2
Setting IP Addresses
Set the slave IP address for each device. Set same network address for all
devices. The following shows an example of setting the IP addresses for use
in this procedure.
Note
After an IP address has been set, check whether the setting is cor-
rect by connecting the personal computer to the device, and then
entering “ping
IP_address
” from the personal computer. For the
EtherNet/IP Unit in the above example, enter “ping 192.168.0.10.”
The setting is correct if the following is returned.
1,2,3...
1.
Setting the IP Address of the Personal Computer
Set the IP address of the personal computer.
2.
Setting the IP Address of the EtherNet/IP Unit
Set the IP address of the EtherNet/IP Unit. Refer to
Common Procedure 6-
1
. Address Setting for OMRON EtherNet/IP Units.
3.
Setting the IP Addresses of the EtherNet/IP Slave Units
The IP address of an EtherNet/IP Slave Unit can be set using any of the
following three methods.
• Setting the IP address with a CIP message (Network Configurator)
• Setting the IP address with a BOOTP/DHCP server
• Setting the IP address with the rotary switches
■
Setting the IP Address with a CIP Message (Network Configurator)
The Network Configurator can be used to set IP addresses.
This method involves first using the rotary switches to set an initial IP address,
and then using the Network Configurator to set the desired IP address.
Personal computer
255.255.255.0
192.168.0.20
255.255.255.0
192.168.0.10
255.255.255.0
192.168.0.100
EtherNet/IP Unit
IP address
Subnet mask
Default gateway
EtherNet/IP Slave Unit
Not set.
Not set (0.0.0.0).
Not set.
This part is set to the same value for
all devices.
Pinging 192.168.0.10 with 32 bytes of data:
Reply from 192.168.0.10: bytes=32 time=1ms TTL=255
Reply from 192.168.0.10: bytes=32 time=1ms TTL=255
Reply from 192.168.0.10: bytes=32 time<1ms TTL=255
Reply from 192.168.0.10: bytes=32 time<1ms TTL=255
Ping statistics for 192.168.0.10:
Packets: Sent = 4, Received = 4, Lost = 0 (0% loss),
Approximate round trip times in milli-seconds:
Minimum = 0ms, Maximum = 1ms, Average = 0ms
Summary of Contents for ERT1 Series
Page 1: ...OPERATION MANUAL Cat No W481 E1 02 EtherNet IP Slave Units ERT1 Series...
Page 2: ......
Page 3: ...ERT1 Series EtherNet IP Slave Units Operation Manual Revised November 2010...
Page 4: ...iv...
Page 6: ...vi...
Page 8: ...viii...
Page 14: ...xiv...
Page 58: ...38 Recommended Network Devices Section 2 2...
Page 62: ...42 Basic Specifications of Slave Units Section 3 1...
Page 78: ...58 Screw less Clamp Terminals Section 4 2...
Page 92: ...72 Environment resistive Slave Units Section 5 2...
Page 102: ...82 Maintenance and Replacement Section 7 3...
Page 106: ...86 Revision History...
Page 107: ......